![JUMO Ex-i Скачать руководство пользователя страница 9](http://html1.mh-extra.com/html/jumo/ex-i/ex-i_safety-manual_2031087009.webp)
9
2 Safety requirements and installation instructions
2.6
Safety data in accordance with ATEX and IECEx
Intrinsically safe sensor input
Max. output voltage U
o
9.56 V
Max. output current I
o
10.3 mA
Max. output power P
o
25 mW
Group
IIB/IIIC
Max. external inductance L
o
1000 mH
Max. external capacitance C
o
26 µF
Additional text
Simple circuit
Group
IIB/IIIC
Max. external inductance L
o
100 mH
5 mH
1 mH
10 µH
Max. external capacitance C
o
1 µF
1 µF
1 µF
1 µF
Additional text
Mixed circuit
Group
IIC
Max. external inductance L
o
300 mH
Max. external capacitance C
o
3.6 µF
Additional text
Simple circuit
Group
IIC
Max. external inductance L
o
100 mH
50 mH
5 mH
1 mH
10 µH
Max. external capacitance C
o
510 nF
580 nF
600 nF
600 nF
600 nF
Additional text
Mixed circuit
Max. internal inductance L
i
Negligible
Max. internal capacitance C
i
11 nF
Safety-related maximum voltage
U
m
Supply terminals
253 V AC/DC
Output terminals
250 V AC / 120 V DC
Содержание Ex-i
Страница 1: ...70754000T99Z001K000 V1 00 EN 00751108 2021 03 17 JUMO Ex i Isolating Switch Amplifier Safety Manual...
Страница 2: ......
Страница 10: ...2 Safety requirements and installation instructions 10...
Страница 18: ...4 Configuration 18...
Страница 20: ...5 Comparison of the safety data 20...
Страница 30: ...6 Safety related applications 30...
Страница 31: ......