9 Technical data
85
9.1.5
Resistance/potentiometer
9.2
Measuring circuit monitoring
Designation
Measuring range
Measuring accu-
racy
Ambient temperature
influence
Sensor type resistance/potentiometer
max. 10 k
Ω
±10
Ω
≤
±0.01 %/K
Deviation of 22 °C
Connection type
Potentiometer with 2-, 3- or 4-wire circuit
Sensor line resistance
≤ 50
Ω
per line for 3- and 4-wire circuit
≤ 100
Ω
line resistance for 2-wire circuit
Resistance values
Freely programmable within the limits in steps of 0.1
Ω
Special features
Measuring range scaling, adjustable
Measuring probe
Out of range
Probe/cable break
Probe/cable short circuit
RTD temperature probe
is detected
is detected
is detected
Resistance transmitter
is detected
is detected
is not detected
Thermocouple (single)
is detected
is detected
is not detected
Double thermocouple
is detected
is detected
is detected
Voltage
0 to 10 V
0 to 1 V
is detected
is detected
is not detected
is not detected
is not detected
is not detected
Содержание dTRANS T06
Страница 16: ...3 Mounting 16 3 Mounting 3 1 Dimensions...
Страница 18: ...3 Mounting 18 3 4 Dismounting Place screwdriver in release catch and press upwards 1 Remove housing upwards 2...
Страница 30: ...5 Startup of the device 30 Here is a summary of the parameters from the figure above...
Страница 31: ...5 Startup of the device 31...
Страница 40: ...6 Safety Manual 40 0 0 6 6 0 0 6 6 7 0 0 6 0 0 6 0 0 6 0 0 6 8...
Страница 59: ...6 Safety Manual 59...
Страница 79: ...8 Device info 79...
Страница 103: ...12 What to do if 103...
Страница 104: ...13 Certificates 104 13 Certificates SEBS A 093409 14 V1 0...
Страница 110: ...13 Certificates 110...
Страница 111: ......