4 Electrical connection
4
Electrical connection
4.1
Installation notes
DANGER!
Injury to persons caused by electric shock
The electrical connection must only be carried out by qualified personnel!
4.2
Connection diagram
Ensure that the fuses of the load circuits are suitable for the maximum load currents to avoid damage to
the device.
The electromagnetic compatibility meets standard EN 61326.
Do not connect any additional loads to the voltage supply of the device.
The device is not suitable for installation in potentially explosive areas.
In addition to a faulty installation, incorrectly set values could also impair the orderly function of the down-
stream process or lead to other damage. Access to settings should only be given to qualified personnel.
Please observe the corresponding safety regulations in this context.
Output 470
Output 471
Output 475 - 477
1 PNP switching output
2 PNP switching outputs
1 PNP switching 1 analog
output
Voltage
supply
Voltage
supply
Voltage
supply
1 L+
DC 12(14) to 30 V
1 L+
DC 12(14) to 30 V
1 L+
DC 12(14) to 30 V
3 L-
(GND)
3 L-
(GND)
3 L-
(GND)
Output
Output
Output
4 K1
Highside open collector
max. 250 mA
2 K2
Highside open collector
max. 250 mA
2 analog
0(4) to 20 mA/0 to 10 V
2
nc
4 K1
4 K1
Highside open collector
max. 250 mA
5
Interface
5
Interface
5
Interface
1
2
3
4
5
L-
K1
L+
1
2
3
4
5
L-
K1
K2
L+
1
2
3
4
5
L-
K1
L+