According to DIN EN 806-5:2012, every technical plant requires regular servicing and inspection. The
inspection must be carried out every six month by trained personnel, the maintenance at an annual interval,
in the course of the maintenance of the relevant heating and / or cooling system. This is done by the JUDO
Customer Service or an authorized specialist company, which will also take care of the replacement of
defective parts or wearing parts.
We recommend that you set up a customer service contract, so that your JUDO sludge separator can be
regularly tested for fault free operation.
The magnesium anode has to be inspected during operation every six months, and must be
replaced depending on the degree of consumption.
The magnetic rods should be checked at regular intervals for correct insertion.
6.1
Replacing the magnesium anode
Switch off the on-site circulation pump or open the on-site shut-off valve in the bypass.
Connect the onsite shut-off valve (1+2) on the inlet and outlet side of the JUDO FERROCLEAN
sludge separator.
Unscrew the holder (SW 41) of the magnesium anode.
Remove the used up magnesium anode from the holder and install the new magnesium anode
properly on the holder.
Screw in the holder properly and tightly, ensure that the flat gasket is correctly seated.
Open the shut-off valve (1+2) on the inlet and outlet side of the JUDO FERROCLEAN sludge
separator.
Switch on the onsite circulation pump or close the onsite shut-off valve in the bypass.
6.2
Replacing the magnetic rods
The JUDO FERROCLEAN sludge separator must be properly flushed (see Chap. 5.3.1 or 5.3.2).
Cluse the sludge shut-off valve (7) after flushing.
Remove the base plate of the support legs.
Pull out the magnetic rods (8) and insert new magentic rods properly up to the stop.
Mount the base plate of the support legs properly again.
Restore proper circulation (see Chap. 5.3.1 or 5.3.2).
6.3
Spare parts
Designation
Order no.
JUDO magnesium anode *
8430229
Complete magnetic rod
2050178
Tab. 10: Spare parts
*
Wear part