Surge Protective Devices

Installation, Operation 
and Maintenance Manual

PN 750-0111-001 B00

Surgitron I

S u r g e

   

P r O T e C T I O N

Joslyn

TM

Содержание Surgitron I 1260

Страница 1: ...Surge Protective Devices Installation Operation and Maintenance Manual PN 750 0111 001 B00 Surgitron I S u r g e P R O T E C T I O N Joslyn TM ...

Страница 2: ...onnection Diagrams 5 6 Single Phase 2 Wire 5 Split Phase 3 Wire 3 Phase 4 Wire Wye 5 3 Phase 3 Wire Delta 5 3 Phase 4 Wire High Leg Delta 5 3 Phase 3 Wire Corner Grounded Delta 6 Conductor Routing 6 Upstream Over Current Protection Device 7 Electrical Connections 7 Conductor Sizing 8 Mounting 8 Conduit Openings and Enclosure Mounting Dimensions 8 9 Connecting Form C Dry Contacts 10 Verification an...

Страница 3: ... 3 Phase Wye 3 Phase High Leg Delta or split phase device See NEC Article 250 If the transformer is not accessible check the main service disconnect panel for the N G bond Lack of a proper bond will damage and void the warranty W A R N I N G Do not HIPOT the Surgitron I Series units or the electrical system to which the Surgitron I Series unit is connected without disconnecting the Surgitron I ser...

Страница 4: ...N VOLTAGE RANGE L L VOLTAGE RANGE CONFIGURATION 1260 45 85 120 108 132 N A 1 Phase 2 Wire Ground 1261 45 85 230 207 253 N A 1 Phase 2 Wire Ground 1265 45 85 85 M 85 MN 120 240 108 132 216 264 1 Phase 3 Wire Ground 1266 45 85 220 440 to 240 480 198 264 396 528 3 Phase 3 Wire Delta Corner Grounded 1450 85 220 240 N A 198 264 3 Phase 3 Wire Ungrounded Delta 1451 85 440 480 N A 396 528 3 Phase 3 Wire ...

Страница 5: ...ntenAnce MAnuAl Wiring Connection Diagrams Figure 1 Single Phase 2 Wire Models 1260 1261 Figure 2 Split Phase 3 Wire Model 1265 Figure 3 3 Phase 4 Wire Wye Models 1455 1456 1457 Figure 4 3 Phase 3 Wire Delta Models 1450 1451 L SPD N G L1 L2 SPD N G ...

Страница 6: ...d above should be addressed during the design of an installation to reserve a suitable place for the product next to its point of connection to the electrical system The selected mounting location should allow for the shortest possible conductor runs and a direct route with a minimum of bends If bends are required they should be sweeping bends 12 radius Do not make sharp 90 bends for appearance pu...

Страница 7: ...thout an upstream over current protection device OCPD If installing as a Type 2 SPD the use of an external OCPD is recommended If the SPD is connected to a dedicated OCPD a 60A breaker is recommended The advantage of using a dedicated over current device for the SPD even if the upstream breaker is 200A or less is that it allows the SPD to be de energized during service without disturbing the elect...

Страница 8: ...f installation That is to say the protection levels to connected equipment will be better with this type of installation Shunt Connecting The protector is connected in parallel to the service mains Keep the cables to the protector as short and straight as possible The cable lugs supplied with the protector will accommodate a cable size range of AWG 4 2 0 20 70 mm 2 a cable size of AWG 2 is normall...

Страница 9: ...261 1265 1266 1452 1455 1456 1457 6 00 8 90 10 75 11 50 4 20 13 50 12 75 8 00 10 90 5 20 Ø 31 Mounting Hole 4 Places 6 20 15 50 14 75 10 00 12 90 Possible Locations for Conduit Holes Metal NEMA 4 IP66 Enclosure Ø 31 Mounting Hole 4 Places Ø 31 Mounting Hole 4 Places Possible Locations for Conduit Holes Metal NEMA 4 IP66 Enclosure ...

Страница 10: ...contacts 2 and 3 will open and contacts 1 and 2 will close The installer must provide the appropriate raceway and wiring for the monitoring circuit observing the restrictions and conduit openings illustrated in an earlier section of this manual The install must route the monitoring conductors to the terminal blocks on the door mounted main monitoring board Route the wire to allow the door to be op...

Страница 11: ...or assistance 800 238 5000 Technical Assistance Returns and Warranty Procedures Our staff is ready to support you and answer any questions Monday through Friday 8 00 a m to 5 00 p m EST at 800 238 5000 Units are warranted for a period of 5 years from date of purchase In the event that any module or subassembly within the SPD fails to perform as specified during the warranty period call our Technic...

Страница 12: ...TED TO THE WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED The liability of Seller under this warranty is expressly limited to the replacement or repair of the defective part thereof at Seller s sole option IN NO EVENT SHALL SELLER BE LIABLE FOR SPECIAL INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY KIND OR CHARACTER NOR SHALL SELLER S LIABILITY EVER EXCEED THE...