If flame is lost, the control de-energizes the gas
valve within 2.0 second and counts the flame loss.
If flame has been lost more than 5 times within the
same call for heat, the control locks out flashing "5"
on the LED. If flame has been lost less than 5 times,
the control attempts re-ignition after a 30 second
inter-purge period.
High heat
The ICB recognizes a call for 2nd stage heat when
W2 is energized. The control energizes the high gas
output.
If the call for 2nd stage heat goes away and the 1st
stage call remains, the control de-energizes the high
gas valve and returns to low heat operation.
Response to loss of W1, low pressure switch, and
flame are identical to low heat operation.
Post Purge
The ICB runs the induced draft motor for a 5 second
post-purge period, then de-energizes the inducer. If
a call for heat occurs during post-purge, the control
finishes the post-purge, drops inducer out to re-
prove open pressure switch before continuing with
the heat cycle.
Lockout
While in lockout, the ICB keeps the main gas valve
and induced draft motor de-energized.
Lockouts due to failed ignition or flame losses may
be reset by removing the call for heat (W1) for
more than 1 second, but less than 20 seconds, or
by removing power from the control for over 0.25
seconds. The control will automatically reset lockout
after 60 minutes.
Lockouts due to detected internal control faults will
reset after 60 minutes or power interruption.
High temperature limit switch
If the high temperature limit switch is open the
control will run the inducer, de-energize the gas
valve, and flash "6" on the LED. When the high
temperature switch closes, the control will restart
the ignition sequence beginning with pre-purge.
If the high temperature limit is open for more than
6 minutes continuously during a call for heat, it is
assumed that the main blower has failed and the
control shall enter a hard lockout and flash a "9"
on the LED. During the hard lockout, the control
will continue to run the inducer as long as the limit
switch is open. If the limit switch recloses in this
hard lockout condition, the inducer will run a post
purge and then shutoff. The control shall remain
locked out until power is removed and shall not
reset automatically.
Roll-out switch
If the roll-out switch opens for more than 0.25
seconds, the ICB will run the inducer for a post-
purge period, immediately de-energize the gas
valve, and flash "7" on the LED.
If the roll-out switch closes, the control shall remain
locked out until power removed or "W" is removed.
Rollout switch lockout shall not reset automatically.
Power interruptions
Power interruptions less than 0.80 seconds shall
not cause the ICB to interrupt the heat sequence.
Power interruptions over 0.250 seconds will cause
the control reset lockout and ignition trial counters.
Power interruptions of any duration shall not
cause lockout or any operation requiring manual
intervention.
Flame present with Gas off
If flame is sensed for longer than 2.0 seconds during
a period when the gas valve should be closed, the
ICB will enter lockout. The control will turn on the
inducer blower while the flame is present.
Welded gas valve relay response
If either or both Main and 2nd Stage Gas valve
outputs are sensed to be off for more than 1 second
when commanded to be
ON
the ICB shuts off all
outputs and enters lockout.
If the Main valve output is sensed to be energized
for more than 1 second when commanded to be off,
the control de-energizes the induced draft motor
(if flame is not present) to attempt to open the
pressure switch to de-energize the gas valve. If the
Main gas valve is still sensed as energized after the
inducer has been off for 15 seconds, the control
re-energizes the inducer to attempt to vent the
unburned gas. In either case, the control locks out.
INSTALLATION MANUAL ZY SERIES 3 - 10 ton 60 Hertz R-410A
120
Johnson Controls Ducted Systems
Содержание ZY Series
Страница 2: ...2 INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A Johnson Controls Ducted Systems ...
Страница 8: ...Nomenclature INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 8 Johnson Controls Ducted Systems ...
Страница 139: ...Start Up Sheet INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 139 Johnson Controls Ducted Systems ...
Страница 140: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 140 Johnson Controls Ducted Systems ...
Страница 141: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 141 Johnson Controls Ducted Systems ...
Страница 142: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 142 Johnson Controls Ducted Systems ...
Страница 143: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 143 Johnson Controls Ducted Systems ...