Setpoints screen
Figure 27: Setpoints screen
This screen provides a convenient location for programming the most common setpoints involved
in the chiller control. This screen also serves as a gateway to the
for defining the setup
of general system parameters.
Table 44: Display only fields
Field/LED name
Description
Leaving Chilled Liquid
Temperature - Setpoint
Displays the present Active setpoint to which the chiller is operating whether controlled
remotely or locally.
Leaving Chilled Liquid
Temperature Cycling -
Shutdown
Displays the Leaving Chilled Liquid Temperature at which the chiller will shut down to avoid
over-cooling LCHLT below setpoint in low load situations.
Leaving Chilled Liquid
Temperature Cycling – Restart
Displays the Leaving Chilled Liquid Temperature at which the chiller will restart after it has
shut down due to over-cooling temperature.
Input Current Limit Setpoint Displays the active Input Current Limit setpoint. This is the minimum of the locally or remote
(received via 0 VDC to 10 VDC, 2 VDC to 10 VDC, 0 mA to 20 mA, or 4 mA to 20 mA input or
PWM) programmed Current Limit setpoint or pulldown limit. In BAS (ISN) remote mode, the
remote setpoint is received from the SC-Equip Gateway interface.
YVAM Control Center
60
Содержание YORK YVAM 0350
Страница 2: ...2 YVAM Control Center...
Страница 10: ...Figure 4 Variable speed drive nomenclature YVAM Control Center 10...
Страница 15: ...Figure 8 System piping and instrumentation diagram P ID 15 YVAM Control Center...
Страница 118: ...Figure 47 Drive logic board Callout Component Callout Component A U35 B U38 C U37 D U36 YVAM Control Center 118...
Страница 154: ...Figure 62 Sample printout status or history YVAM Control Center 154...
Страница 155: ...Figure 63 Sample printout status or history continued 155 YVAM Control Center...
Страница 156: ...Figure 64 Sample printout setpoints YVAM Control Center 156...
Страница 157: ...Figure 65 Sample printout setpoints continued 157 YVAM Control Center...
Страница 158: ...Figure 66 Sample printout schedule YVAM Control Center 158...
Страница 159: ...Figure 67 Sample printout sales order 159 YVAM Control Center...
Страница 160: ...Figure 68 Sample printout security log report YVAM Control Center 160...