Magnetic bearing controller details screen
Figure 18: Magnetic bearing controller details screen
This screen displays the orientation of the magnetic bearing axes relative to the compressor
driveline similar to the MBC screen. Additional pertinent parameters transmitted to the control
panel from the MBC are displayed on this screen. Many parameters are shown in the diagram
in the locations they represent. The left end of the motor shaft graphic represents the low stage
(single stage) impeller end bearing. The right end of the motor shaft graphic represents the
opposite end bearing.
Table 24: Display only fields
Field/LED name
Description
Z1 Temperature
Displays the temperature measured at the impeller end bearing assembly.
A13 Unbalance / B13 Unbalance
Magnitude of motion at 1x rotation in each of two vectors at the 1-stage impeller end.
A24 Unbalance / B24 Unbalance
Magnitude of motion at 1x rotation in each of two vectors at the opposite 1-stage
impeller end.
Z2 Temperature
Displays the temperature measured at the opposite impeller end bearing assembly.
Z12 Vibration
Displays the vibration amplitude for specific frequencies measured axially by the
position sensors.
Magnetic bearing currents as described for the MBC screen are repeated on this
screen:
•
W1 (Current)
•
V1 (Current)
•
Z1 (Current)
•
V3 (Current)
•
W3 (Current)
•
W2 (Current)
•
V2 (Current)
•
Z2 (Current)
•
V4 (Current)
•
W4 (Current)
[MBC Status] AVR (LED)
Indicates the MBC is reporting its automatic vibration reduction feature is active via
Modbus Data.
YVAM Control Center
44
Содержание YORK YVAM 0350
Страница 2: ...2 YVAM Control Center...
Страница 10: ...Figure 4 Variable speed drive nomenclature YVAM Control Center 10...
Страница 15: ...Figure 8 System piping and instrumentation diagram P ID 15 YVAM Control Center...
Страница 118: ...Figure 47 Drive logic board Callout Component Callout Component A U35 B U38 C U37 D U36 YVAM Control Center 118...
Страница 154: ...Figure 62 Sample printout status or history YVAM Control Center 154...
Страница 155: ...Figure 63 Sample printout status or history continued 155 YVAM Control Center...
Страница 156: ...Figure 64 Sample printout setpoints YVAM Control Center 156...
Страница 157: ...Figure 65 Sample printout setpoints continued 157 YVAM Control Center...
Страница 158: ...Figure 66 Sample printout schedule YVAM Control Center 158...
Страница 159: ...Figure 67 Sample printout sales order 159 YVAM Control Center...
Страница 160: ...Figure 68 Sample printout security log report YVAM Control Center 160...