SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
JOHNSON CONTROLS
51
FORM 160.54-O1
ISSUE DATE: 9/10/2014
2
OVERVIEW
This screen displays a cutaway view of the chiller con-
denser, along with the liquid refrigerant level sensor
and variable orifice. Setpoints relating to the liquid lev-
el control are maintained on this screen. Through ani-
mation, the variable orifice position is displayed. Also,
the refrigerant flow control valve (variable orifice) can
be manually operated.
A variable orifice is used to control the condenser re-
frigerant level to the Refrigerant Level Setpoint. The
control thresholds are applied in two different zones,
as determined by the error relationship between the
actual refrigerant level and the level setpoint. Zone 1
parameters are used when the error is less than or equal
to 9%. Zone 2 parameters are used when the error is
greater than 9%. When transitioning from Zone 2 to
Zone 1, the error must be less than or equal to 9% for
60 seconds before the Zone 1 parameters are used. If
the error is greater than 9%, the Zone 2 parameters are
immediately implemented.
Requires a login access level of SERVICE.
Service Technicians refer to the OptiView
Control Center - Service Instructions
(Form 160.54-M1) for operation instruc-
tions and explanation of all programmable
setpoints and displayed values.
DISPLAY ONLY
Refrigerant Level Position
Displays the present level of the liquid level control.
The refrigerant level is animated in the cutaway view of
the condenser. When the actual level is 0% to 15%, the
level is shown about 50% full. When the actual level is
16% to 31%, the level is shown about 60% full. When
the actual level is 32% to 47%, the level is shown about
70% full. When the actual level is 48% to 63%, the
level is shown about 80% full. When the actual level
is 64% to 79%, the level is shown as about 90% full.
Actual levels above 79% shown as 100% full.
REFRIGERANT LEVEL CONTROL SCREEN
(SOFTWARE VERSIONS C.MLM.01.14.XXX AND LATER OR C.OPT.01.14.306 AND LATER)
LD10703
FIGURE 15 -
REFRIGERANT LEVEL CONTROL SCREEN (SOFTWARE VERSIONS C.MLM.01.14.XXX AND
LATER OR C.OPT.01.14.306 AND LATER)
Содержание YORK YK Style G OPTIVIEW
Страница 38: ...JOHNSON CONTROLS 38 FORM 160 75 O1 111 NOTES ...
Страница 242: ...FORM 160 54 O1 ISSUE DATE 9 10 2014 JOHNSON CONTROLS 202 SECTION 3 DISPLAY MESSAGES THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 258: ...FORM 160 54 O1 ISSUE DATE 9 10 2014 JOHNSON CONTROLS 218 NOTES ...
Страница 266: ...JOHNSON CONTROLS 6 FORM 160 75 N1 ISSUE DATE 4 30 2014 THIS PAGE INTENTIONALLY LEFT BLANK ...