SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
JOHNSON CONTROLS
41
FORM 160.54-O1
ISSUE DATE: 9/10/2014
2
HEAT PUMP SCREEN
(SOFTWARE VERSION C.OPT.01.23.307 AND LATER)
LD15425
FIGURE 11 -
HEAT PUMP SCREEN (SOFTWARE VERSION C.OPT.01.23.307 AND LATER)
OVERVIEW
Heat Pump is an available option on certain models
of YK chillers. The feature is enabled and disabled on
the SETUP Screen. When enabled, this HEAT PUMP
Screen is accessible from the CONDENSER Screen.
The Heat Pump control can be switched between Heat-
ing mode and Cooling mode using the Operational mode
setpoint on this screen. In Heating mode, the chiller con-
trols the Leaving Condenser Liquid Temperature to its
setpoint. In Cooling mode, the chiller controls the Leav-
ing Chilled Liquid Temperature to its setpoint.
When Heat Pump is enabled, certain conditions are
automatically set as follows: The Heat Recovery and
Head Pressure Control options are disabled and locked.
The Condenser Temperature Range Setpoint is set to
Extended. The Condenser High Pressure Warning
Setpoint threshold is set to 193 PSIG.
The Quick Start feature is only available in Cooling
mode and is automatically disabled when Heating
mode is selected.
If chiller is equipped with a VSD, it will operate at full
speed (50Hz or 60Hz) at all times in Heating mode. In
Cooling mode, it operates normally.
All setpoints pertinent to this feature are maintained on
this screen.
DISPLAY ONLY
Leaving Condenser Liquid Temperature
Displays the temperature of the liquid as it leaves the
condenser
Return Condenser Liquid Temperature
Displays the temperature of the liquid as it enters the
condenser
Leaving Condenser Liquid Temperature
Setpoints – Setpoint
Displays the active Leaving Condenser Liquid Tem-
perature Setpoint to which the Heat Pump is operat-
ing, whether controlled locally or remotely, in Heating
mode.
Leaving Condenser Liquid Temperature
Setpoints – Remote Range
Displays the temperature range over which a remote
device (in Analog or Digital Remote mode) can reset
the Heat Pump Leaving Condenser Liquid Tempera-
Содержание YORK YK Style G OPTIVIEW
Страница 38: ...JOHNSON CONTROLS 38 FORM 160 75 O1 111 NOTES ...
Страница 242: ...FORM 160 54 O1 ISSUE DATE 9 10 2014 JOHNSON CONTROLS 202 SECTION 3 DISPLAY MESSAGES THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 258: ...FORM 160 54 O1 ISSUE DATE 9 10 2014 JOHNSON CONTROLS 218 NOTES ...
Страница 266: ...JOHNSON CONTROLS 6 FORM 160 75 N1 ISSUE DATE 4 30 2014 THIS PAGE INTENTIONALLY LEFT BLANK ...