SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
JOHNSON CONTROLS
29
FORM 160.54-O1
ISSUE DATE: 9/10/2014
2
Setpoint. However, the Offset being used will auto-
matically change based on the values programmed for
the Leaving Chilled Liquid Temperature Setpoint and
the Shutdown Setpoint, to prevent the Leaving Chilled
Liquid Temperature from going below the minimum
allowed value: 36°F (water), 34°F (water with smart
freeze enabled) or 6°F (brine). For example, if the
Leaving Chilled Liquid Temperature Setpoint is set to
45°F (water) and the Shutdown Setpoint is set to 4°F,
the Effective Offset is displayed as 4°F. If the leaving
setpoint is lowered to 38°F, the Effective Offset will
change to 2°F. If the leaving chilled setpoint is raised
back to 45°F, the Effective Offset will revert back to
the Shutdown Setpoint. With software versions prior
to C.OPT.01.18.307, the value is displayed as Offset
and reflects the programmed value only, not the offset
being used.
Leaving Chilled Liquid Temperature Cycling
Offset – Restart
Access Level Required: OPERATOR
This value allows the user to specify the Leaving
Chilled Liquid Temperature at which the chiller will
restart after a shutdown on a LEAVING CHILLED
LIQUID – LOW TEMPERATURE cycling shutdown.
This is done by defining an offset above the Leaving
Chilled Liquid Temperature Setpoint. It is program-
mable over a range of 0°F to 70°F above the setpoint,
to a maximum restart value of 80°F. The chiller will
automatically restart when this temperature is reached.
This setpoint can be used to reduce chiller cycling by
delaying the chiller restart until the cooling load has
increased.
Brine Low Evaporator Cutout
Access Level Required: SERVICE
This value is only available in Brine mode. It allows
the user to specify the Evaporator Pressure at which a
safety shutdown is initiated.
Sensitivity
Access Level Required: SERVICE
This value allows the user to adjust the sensitivity of
the Leaving Chilled Liquid Temperature control.
Smart Freeze (Off / On)
Access Level Required: SERVICE
This value is only available if the chiller is not in Brine
mode. It allows the user to enable the Smart Freeze
Point Operation which allows the chiller to run closer
to the freeze point without shutting down.
Refrigerant (Enabled / Disabled)
Access Level Required: SERVICE
When an Evaporator Refrigerant Sensor has been in-
stalled it must be enabled via this toggle before the
system will utilize the new, enhanced resolution input.
NAVIGATION
Home
Access Level Required: VIEW
Returns user to HOME Screen.
Heat Pump
(Software version C.OPT.01.23.307 and later)
Access Level Required: VIEW
Moves to a sub screen allowing programming and
viewing of the Heat Pump Setpoints and parameters.
Only appears when Heat Pump is enabled on the SET-
UP Screen.
Содержание YORK YK Style G OPTIVIEW
Страница 38: ...JOHNSON CONTROLS 38 FORM 160 75 O1 111 NOTES ...
Страница 242: ...FORM 160 54 O1 ISSUE DATE 9 10 2014 JOHNSON CONTROLS 202 SECTION 3 DISPLAY MESSAGES THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 258: ...FORM 160 54 O1 ISSUE DATE 9 10 2014 JOHNSON CONTROLS 218 NOTES ...
Страница 266: ...JOHNSON CONTROLS 6 FORM 160 75 N1 ISSUE DATE 4 30 2014 THIS PAGE INTENTIONALLY LEFT BLANK ...