SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
JOHNSON CONTROLS
127
FORM 160.54-O1
ISSUE DATE: 9/10/2014
2
OVERVIEW
This screen provides a convenient location for pro-
gramming the most common setpoints involved in the
chiller control. This screen also serves as a gateway to
a subscreen for defining the setup of general system
parameters.
DISPLAY ONLY
Leaving Chilled Liquid Temperature –
Setpoint
Displays the present setpoint to which the chiller is
operating whether controlled remotely or locally. This
value could come from a 0 to 20 mA, 4 to 20mA, 0 to
10VDC or 2 to 10VDC input in Analog Remote mode,
PWM signal in Digital Remote mode, E-Link Gateway
interface in ISN mode, or a locally programmed value.
Leaving Chilled Liquid Temperature Cycling –
Shutdown
Displays the Leaving Chilled Liquid Temperature at
which the chiller will shut down to avoid over-cool-
ing the building. This value is calculated by subtract-
ing the Leaving Chilled Liquid Temperature Cycling
Offset – Shutdown from the Leaving Chilled Liquid
Temperature – Setpoint. If this value is below the abso-
lute minimum allowed shutdown temperature the mini-
mum value is displayed.
Leaving Chilled Liquid Temperature Cycling –
Restart
Displays the Leaving Chilled Liquid Temperature at
which the chiller will restart after it has shut down due
to over-cooling temperature. This value is calculated
by adding the Leaving Chilled Liquid Temperature Cy-
cling Offset – Restart to the Leaving Chilled Liquid
Temperature – Setpoint.
Current Limit Setpoint
(Flash Memory Card version C.MLM.01.01 or later)
Displays the active Current Limit Setpoint. In Local
mode, this is the locally programmed Current Limit
Setpoint. In ISN Remote mode, this is the setpoint re-
ceived from the E-Link Gateway interface. In Analog
Remote mode, this is the setpoint received via 0 to
10VDC, 2 to 10VDC, 0 to 20mA or 4 to 20mA input.
In Digital Remote mode, this is the Pulse width Modu-
lation signal input.
SETPOINTS SCREEN
LD14342
FIGURE 43 -
SETPOINTS SCREEN
Содержание YORK YK Style G OPTIVIEW
Страница 38: ...JOHNSON CONTROLS 38 FORM 160 75 O1 111 NOTES ...
Страница 242: ...FORM 160 54 O1 ISSUE DATE 9 10 2014 JOHNSON CONTROLS 202 SECTION 3 DISPLAY MESSAGES THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 258: ...FORM 160 54 O1 ISSUE DATE 9 10 2014 JOHNSON CONTROLS 218 NOTES ...
Страница 266: ...JOHNSON CONTROLS 6 FORM 160 75 N1 ISSUE DATE 4 30 2014 THIS PAGE INTENTIONALLY LEFT BLANK ...