SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
JOHNSON CONTROLS
123
FORM 160.54-O1
ISSUE DATE: 9/10/2014
2
OVERVIEW
This screen allows programming of the winding and
bearing High Temperature Warning/Safety Shutdown
thresholds and the High Vibration Warning/Safety
Shutdown thresholds, along with the vibration input
gain. Also, individual winding temperature sensors can
be disabled on this screen.
DISPLAY ONLY
Motor Windings
Temperature
Displays the Enabled/Disabled status of each winding
sensor. The TEMPERATURE DISABLE Setpoint key
can be used to enable or disable individual winding
temperature sensors. Not shown when Winding Tem-
perature Protection Setpoint on the MOTOR DETAILS
Screen is set to Disabled.
High Winding Temperature Shutdown
Displays the High Winding Temperature safety shut-
down threshold, as programmed with the WINDING
SETUP Setpoint key. Not shown when Winding Tem-
perature Protection Setpoint on the MOTOR DETAILS
Screen is set to Disabled.
Winding Hotspot Allowance
Displays the Winding Hotspot Allowance temperature.
Not shown when Winding Temperature Protection
Setpoint on the MOTOR DETAILS Screen is set to
Disabled.
Motor Bearings
High Vibration Shutdown
Displays the High Vibration safety shutdown threshold
for the Shaft End and Opposite Shaft End bearings. Not
shown when the Motor Vibration Protection Setpoint
on MOTOR DETAILS Screen is set to Disabled. The
threshold used for this setpoint will either be the val-
ues entered by the Vibration Setup Setpoint or values
derived from the Vibration Baseline Setpoints (refer to
). Also displayed is the
Delay, which is the amount of time the vibration must
exceed the shutdown threshold before the shutdown
occurs.
MOTOR SETPOINTS SCREEN
(SOFTWARE VERSION C.OPT.01.22.307 AND LATER)
LD10702b
FIGURE 42 -
MOTOR SETPOINTS SCREEN (SOFTWARE VERSION C.OPT.01.22.307 AND LATER)
Содержание YORK YK Style G OPTIVIEW
Страница 38: ...JOHNSON CONTROLS 38 FORM 160 75 O1 111 NOTES ...
Страница 242: ...FORM 160 54 O1 ISSUE DATE 9 10 2014 JOHNSON CONTROLS 202 SECTION 3 DISPLAY MESSAGES THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 258: ...FORM 160 54 O1 ISSUE DATE 9 10 2014 JOHNSON CONTROLS 218 NOTES ...
Страница 266: ...JOHNSON CONTROLS 6 FORM 160 75 N1 ISSUE DATE 4 30 2014 THIS PAGE INTENTIONALLY LEFT BLANK ...