SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
JOHNSON CONTROLS
69
FORM 160.54-O1
ISSUE DATE: 9/10/2014
2
OVERVIEW
(This feature applies to software version C.MLM.01.10.
xxx (and later) or C.OPT.01.10.302 (and later))
This screen displays information pertinent to the VGD
operation. Also, the VGD can be manually controlled
from this screen.
DISPLAY ONLY
Stall Detector Voltage
Displays the Stall Detector output voltage (x.xxVDC),
as received by the Microboard.
Pre-rotation Vanes Position
Displays the position of the Pre-rotation Vanes over
the range of 0% (fully closed) to 100% (fully open).
Displayed as XXX until calibration procedure is per-
formed by Service Technician.
VGD Closed Limit Switch
(Software version C.OPT.01.23.307 and later)
Displays the status of the VGD Limit Switch. Dis-
played as CLOSED when the switch is closed. This
would be when the VGD is in the fully closed position.
Otherwise, displayed as OPEN.
Diffuser Gap Close (LED)
Illuminates when a close signal is being applied to the
VGD.
Diffuser Gap Open (LED)
Illuminates when an open signal is being applied to the
VGD.
Surge Avoidance Surge Detected (LED)
(Software version C.OPT.01.23.307 and later)
Illuminates momentarily when a surge is detected by
the Surge Protection feature. If equipped with a VSD or
MV VSD, these are only the surges detected while the
drive is running at maximum frequency.
If equipped with software version C.OPT.01.22.307
or earlier, this is displayed as Surge Detected. It illu-
minates momentarily when a surge is detected by the
Surge Protection feature, regardless of the VSD operat-
ing speed.
ACC Surge Detected (LED)
(Software version C.OPT.01.23.307 and later)
Only displayed if equipped with a VSD (in Modbus
Protocol Configuration) or MV VSD. Illuminates mo-
mentarily when a surge is detected by the ACC func-
VARIABLE GEOMETRY DIFFUSER SCREEN
LD15427
FIGURE 21 -
VARIABLE GEOMETRY DIFFUSER SCREEN
Содержание YORK YK Style G OPTIVIEW
Страница 38: ...JOHNSON CONTROLS 38 FORM 160 75 O1 111 NOTES ...
Страница 242: ...FORM 160 54 O1 ISSUE DATE 9 10 2014 JOHNSON CONTROLS 202 SECTION 3 DISPLAY MESSAGES THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 258: ...FORM 160 54 O1 ISSUE DATE 9 10 2014 JOHNSON CONTROLS 218 NOTES ...
Страница 266: ...JOHNSON CONTROLS 6 FORM 160 75 N1 ISSUE DATE 4 30 2014 THIS PAGE INTENTIONALLY LEFT BLANK ...