SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
JOHNSON CONTROLS
65
FORM 160.54-O1
ISSUE DATE: 9/10/2014
2
OVERVIEW
This screen displays a cutaway view of the chiller com-
pressor and all parameters relating to the Surge Pro-
tection feature. All setpoints relating to this screen are
maintained on this screen.
The Surge Protection feature detects surge events and
provides a running count of the surges detected over
the lifetime of the chiller. It allows the user to define
how many surges are excessive and how the control
will react to an excess surge condition. When excess
surging is detected, it can be configured to shutdown
the chiller, or initiate a surge avoidance mode while
allowing it to continue to run or simply display a warn-
ing message. The sensitivity of this surge detection
is set by the Sensitivity Setpoint on this screen. The
surges detected by this feature are also used for the Hot
Gas Bypass feature (Refer to
).
The detection and counting of surges in this feature is
completely independent of the surge detection/counting
performed by the Variable Speed Drive (VSD) Adaptive
Capacity Control (ACC) Surge Detection. The ACC
Surge Detection creates a surge map used to control
the speed of the drive. If equipped with an ACC Board
(new production chillers prior to March 2007), the ACC
Surge Detection is performed there. If not equipped with
an ACC Board, (new production chillers after March
2007), the ACC Surge Detection is performed in the
Microboard (Refer to
OptiView Control Center – Ser-
vice Instructions (Form 160.54-M1)
). With all Medium
Voltage Variable Speed Drives (MV VSD), the ACC
Surge Detection is performed in the Microboard.
Screen shown above as it appears in software version
C.OPT.01.19.307 (and later). The parameters displayed
on this screen vary according to the software version
and the motor starter type as noted below.
DISPLAY ONLY
Delta P/P
A parameter that represents the system differential or
Head Pressure. It is calculated as (condenser pressure
– evaporator pressure) / evaporator pressure.
Surge Window Time
When the chiller enters run mode, this value counts
up to the time programmed as the Count Window Set-
point. When it reaches the Count Window minutes, the
number of surge events in the oldest minute is discard-
ed and the number of surge events in the most recent
SURGE PROTECTION SCREEN
LD13827
FIGURE 20 -
SURGE PROTECTION SCREEN
Содержание YORK YK Style G OPTIVIEW
Страница 38: ...JOHNSON CONTROLS 38 FORM 160 75 O1 111 NOTES ...
Страница 242: ...FORM 160 54 O1 ISSUE DATE 9 10 2014 JOHNSON CONTROLS 202 SECTION 3 DISPLAY MESSAGES THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 258: ...FORM 160 54 O1 ISSUE DATE 9 10 2014 JOHNSON CONTROLS 218 NOTES ...
Страница 266: ...JOHNSON CONTROLS 6 FORM 160 75 N1 ISSUE DATE 4 30 2014 THIS PAGE INTENTIONALLY LEFT BLANK ...