SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
JOHNSON CONTROLS
61
FORM 160.54-O1
ISSUE DATE: 9/10/2014
2
OVERVIEW
This screen displays a cutaway view of the chiller com-
pressor, revealing the Proximity Probe sensor and provides
the capability of calibrating the Proximity Probe sensor.
Requires a login access level of SERVICE.
Service Technicians refer to the OptiView
Control Center - Service Instructions
(Form 160.54-M1) for operation instruc-
tions and explanation of all programmable
setpoints and displayed values.
DISPLAY ONLY
High Speed Thrust Bearing Proximity Position
Displays the distance between the high-speed thrust
collar and the Proximity Probe that is used to measure
the position.
High Speed Thrust Bearing Proximity
Reference Position
Displays the presently defined offset reference posi-
tion. This value is defined at the conclusion of a cali-
bration sequence.
Oil Pressure
Displays the pressure differential between the high
side oil pressure transducer (compressor bearing input)
and the low side oil pressure transducer (oil sump). The
displayed value includes offset pressure derived from
auto-zeroing during the System Prelube. If either of the
transducers used to calculate this differential is out of
range, the display field will show XX.X.
Calibration in Progress (LED)
Indicates that the calibration sequence is in progress.
Calibration Messages
These are text messages which step the user through
the calibration process and indicate its success or
failure.
PROGRAMMABLE
Enter Reference
Press this key to enter the reference position manually.
PROXIMITY PROBE CALIBRATION SCREEN
(STYLE E AND EARLIER CHILLERS WITH G, H, OR J COMPRESSORS
AND STYLE F AND LATER CHILLERS WITH J OR H3 COMPRESSORS)
00305VIP
FIGURE 18 -
PROXIMITY PROBE CALIBRATION SCREEN (STYLE E AND EARLIER CHILLERS WITH G, H,
OR J COMPRESSORS AND STYLE F AND LATER CHILLERS WITH J OR H3 COMPRESSORS)
Содержание YORK YK Style G OPTIVIEW
Страница 38: ...JOHNSON CONTROLS 38 FORM 160 75 O1 111 NOTES ...
Страница 242: ...FORM 160 54 O1 ISSUE DATE 9 10 2014 JOHNSON CONTROLS 202 SECTION 3 DISPLAY MESSAGES THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 258: ...FORM 160 54 O1 ISSUE DATE 9 10 2014 JOHNSON CONTROLS 218 NOTES ...
Страница 266: ...JOHNSON CONTROLS 6 FORM 160 75 N1 ISSUE DATE 4 30 2014 THIS PAGE INTENTIONALLY LEFT BLANK ...