SLRS SEISMIC ISOLATOR INSTALLATION AND ADJUSTMENT
To install and adjust mounts:
1. Supports for mountings must be leveled to instal-
lation's acceptable tolerances.
2. Mountings not subjected to seismic or wind forces
do not require bolting to supports.
3. Mountings subjected to seismic or wind forces must
be bolted or welded in position.
4. If mountings are welded in position, remove lower
friction pad before welding.
5. Set mountings with top channels held in place by
the lower restraining nuts and limit stops.
6. Place equipment on mountings and secure by bolt-
ing or welding.
7. Hold lower restraining nut in place and turn verti-
cal limit stop bolt counter-clockwise until there
"D" Tap - 4 Holes unless
otherwise requested
Adjustment
Bolt
Vertical Limit
Stops-Out of
contact during
normal operation
Non-Skid Neoprene Pad-
Pad can be removed if
mounts are welded
into position.
Enclosed
Steel
Housing
Internal
Neoprene
Acoustical
Pad
Lower
Restraining
Nut
Rubber
Snubbing
Collar
MBD -Max
Bolt
Diameter
SHIPPED & INSTALLED
AFTER ADJUSTMENT
1/4"
1/8"
LIMIT STOP
BOLT
LOWER
RESTRAINING
BOLTS
LD10568
Units shipped before June 15, 2008
is a 1/8" gap between the bolt head and the steel
washer.
8. Turn adjustment bolt 8 turns on each mount.
9. Take one additional complete turn on each adjust-
ment bolt in sequence until the top plate lifts off
of the lower restraining nuts. Take no additional
turns on that mount. Continue with equal turns on
the other mounts until the top plates lift off of the
lower restraining nuts of all mounts.
10. Hold the limit stop bolt in place and turn the lower
restraining nut clockwise and tighten it against
the stanchion. Repeat the same procedure on all
mounts.
11. Top plate should remain at a fixed elevation, plus
or minus 1/8".
Содержание YORK Tempo YLAA Series
Страница 4: ...JOHNSON CONTROLS 4 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 12: ...JOHNSON CONTROLS 12 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 14: ...JOHNSON CONTROLS 14 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 18: ...JOHNSON CONTROLS 18 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 36: ...JOHNSON CONTROLS 36 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 49: ...FORM 150 72 NM1 1020 49 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 71: ...FORM 150 72 NM1 1020 71 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 73: ...FORM 150 72 NM1 1020 73 JOHNSON CONTROLS 5 5...
Страница 75: ...FORM 150 72 NM1 1020 75 JOHNSON CONTROLS 5 5...
Страница 77: ...FORM 150 72 NM1 1020 77 JOHNSON CONTROLS 5 5...
Страница 79: ...FORM 150 72 NM1 1020 79 JOHNSON CONTROLS 5 5...
Страница 81: ...FORM 150 72 NM1 1020 81 JOHNSON CONTROLS 5 5...
Страница 83: ...FORM 150 72 NM1 1020 83 JOHNSON CONTROLS 5 5...
Страница 85: ...FORM 150 72 NM1 1020 85 JOHNSON CONTROLS 5 5 LD13901...
Страница 87: ...FORM 150 72 NM1 1020 87 JOHNSON CONTROLS 5 5...
Страница 89: ...FORM 150 72 NM1 1020 89 JOHNSON CONTROLS 5 5 LD13232...
Страница 90: ...JOHNSON CONTROLS 90 FORM 150 72 NM1 1020 Technical Data DUAL PUMP WIRING LD13237 FIG 21 DUAL PUMP WIRING...
Страница 91: ...FORM 150 72 NM1 1020 91 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 92: ...JOHNSON CONTROLS 92 FORM 150 72 NM1 1020 Technical Data WIRING LD13238 FIG 22 WIRING...
Страница 93: ...FORM 150 72 NM1 1020 93 JOHNSON CONTROLS 5 5 LD13239...
Страница 160: ...JOHNSON CONTROLS 160 FORM 150 72 NM1 1020 Unit Operation FIG 28 CONDENSER FAN LOCATIONSWIRING DIAGRAMS...
Страница 176: ...JOHNSON CONTROLS 176 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 191: ...FORM 150 72 NM1 1020 191 JOHNSON CONTROLS 10 NOTES...