Johnson Controls York 366-70487 Скачать руководство пользователя страница 7

JOHNSON CONTROLS

7

FORM 160.43-NM4 

ISSUE DATE: 11/12/2012

1

SECTION 1 - GENERAL

APPLICATION

Low Pressure Cutout (LPCO) controls 025 45742 set 

point and deadband settings are factory set for R-11 or 

R-123 duty application as:

   P/N 

 

 

DESCRIPTION

025 45742 002  CONTROL VACUUM SWITCH R-11 LPCO 
 

Use with R-11 refrigerant

025 45742 003  CONTROL VACUUM SWITCH R-123 LPCO 
 

Use with R-123 refrigerant

LPCO controls 

025 45742

 are available as retrofit 

kits, inclusive of installation hardware, for converting 

from the obsolete 

225 15443 002

 LPCO control used 

in Model OT/HT Style “B” and “C” chillers having 

Electronic Control Centers 366 70488, 366 70487, 366 

73582, as:

   P/N 

 

DESCRIPTION

325 45742 602  KIT, CONTROL LPCO R-11 
 

VACUUM SWITCH Use with  

 

R-11 refrigerant

325 45742 603  KIT, CONTROL LPCO R-123 
 

VACUUM SWITCH Use with  

 

R-123 refrigerant

OPERATION

The Low Pressure cutout (LPCO) controls 025 45742 

are actuated by evaporator pressure. The LPCO control 

operates to stop the chiller compressor operation on the 

decrease of the evaporator pressure equivalent to a re-

frigerant temperature of 28° F and permits re-starting, 

(via the start button) when the evaporator pressure in-

creases equivalent to a refrigerant temperature greater 

than 40° F.
LPCO controls 025 45742 set point and deadband set-

tings are factory set for R-11 or R-123 duty applica-

tion. The cutout set point and deadband settings are 

field adjustable as described in section III Testing and 

Adjustments.
LPCO controls 025 45742 are vacuum switches which 

are negative gauge pressure controls that operate at a 

predetermined constant pressure below atmospheric. 

This means that the absolute pressure of the cutout set-

ting will vary with local atmospheric pressure changes. 

LPCO controls 025 45742 require cutout setpoint and 

Before installing, the installation and 

maintenance instructions provided with 

unit must be read and understood.

Before installing, verify the control part 

no. matches the refrigerant duty applica-

tion.
For all applications, a factory set safety 

control should be tested before use.
To avoid damaging control, proof pressure 

and maximum temperature limits stated in 

literature and on nameplates must never 

be exceeded, even by surges in the system. 

Operation of the unit up to maximum 

pressure or temperature is acceptable on 

a limited basis (e.g., start-up, testing) but 

continuous operation must be restricted to 

the designated adjustable range. Excessive 

cycling at maximum pressure or tempera-

ture limits could reduce sensor life.
Vacuum switches are negative gauge 

pressure controls that operate at a pre-

determined constant pressure below at-

mospheric. This means that the absolute 

pressure of the cutout setting will vary 

with local atmospheric pressure changes.  

Vacuum switches require settings verifica

-

tion at installation and require recalibra-

tion if installed elevation is 300 feet or 

more above or below sea level.
Preventative maintenance and periodic 

testing is necessary for critical applica-

tions where damage could endanger 

property or personnel.

These products do not have any field re

-

placeable parts.

Содержание York 366-70487

Страница 1: ...RS STYLE B AND C CONTROL CENTERS 366 70488 366 70487 AND 366 73582 LOW PRESSURE CUTOUT CONTROL P N 025 45742 000 INSTALLATION AND MAINTENANCE Supersedes 160 43 NM4 1206 Form 160 43 NM4 1112 035 21593...

Страница 2: ...als This individual shall also be familiar with and comply with all applicable governmental standards and regulations pertaining to the task in question SAFETY SYMBOLS The following symbols are used i...

Страница 3: ...icy for con tinuous product improvement the information con tained in this document is subject to change without notice Johnson Controls makes no commitment to update or provide current information au...

Страница 4: ...JOHNSON CONTROLS 4 FORM 160 43 NM4 ISSUE DATE 11 12 2012 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 5: ...ting 025 45742 LPCO Control 9 Pressure Connection Piping 10 Wiring 11 SECTION 3 TESTING AND ADJUSTMENTS 13 Tools Needed 13 Secure Chiller From Operation 13 Connect LPCO Pressure Connection To A Calibr...

Страница 6: ...JOHNSON CONTROLS 6 FORM 160 43 NM4 ISSUE DATE 11 12 2012 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 7: ...tments LPCO controls 025 45742 are vacuum switches which are negative gauge pressure controls that operate at a predetermined constant pressure below atmospheric This means that the absolute pressure...

Страница 8: ...At atmospheric pressure the switch contacts are made between the Common and Normally Open terminals and open between the Common and Normally Closed terminals As the pressure falls below the control C...

Страница 9: ...rated in a vertical position with the switch up and pressure con nection down The controls are surface mounted using two mounting ears with holes for 10 screws on either side of the control bracket pl...

Страница 10: ...o pressure connection tight enough to ensure a leak free seal 2 Installing kit supplied Capillary Tube 48 in YORK p n 026 45010 000 a Ensure 1 4 in flare mating surfaces are clean and free of debris o...

Страница 11: ...itch bracket Refer to Figure 3 The three switch terminals are clearly labeled COM MON NORMALLY OPEN and NORMALLY CLOSED Refer to Figures 3 and 4 1 Remove enclosure cover first by removing the one capt...

Страница 12: ...res 1 3 and 4 and ECC Wiring Diagram 8 Use kit supplied wire tie wraps YORK p n 025 09607 000 to bundle and or secure LPCO control wires numbered 47 48 and 49 as needed 9 Reinstall enclosure cover sec...

Страница 13: ...flare half union fitting at the LPCO control pressure con nection 2 Using clean 1 4 in refrigerant hoses connect a controllable vacuum source in series to a digital vacuum gauge and to the 1 4 in ext...

Страница 14: ...7 Repeat steps 4 5 and 6 until the noted CUT OUT setpoint is within the allowable range 8 Once the CUTOUT set point is verified or cali brated then proceed to the switch DEADBAND calibration procedur...

Страница 15: ...k free seal 4 Disconnect the Ohm meter from the switch Com mon and Normally Open terminals 5 Connect the wire numbered 47 to the 025 45742 LPCO control switch terminal labeled as COM MON Refer to Figu...

Страница 16: ...JOHNSON CONTROLS 16 FORM 160 43 NM4 ISSUE DATE 11 12 2012 Section 3 Testing and Adjustments THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 17: ...plated brass Wetted Materials Brass bellows and zinc plated steel spring Weight Approx 1 lb Approvals UNITED STATES AND CANADA UL Listed cUL Certified Pressure UL 508 CSA C22 2 No 14 Files E42272 EUR...

Страница 18: ...USA 17405 1592 800 861 1001 Subject to change without notice Printed in USA Copyright by Johnson Controls 2012 www johnsoncontrols com ALL RIGHTS RESERVED Form 160 43 NM4 1112 Issue Date November 12 2...

Отзывы: