SECTION 8 - MICROPANEL
FORM 201.23-NM2
ISSUE DATE: 3/9/2015
8
LD10605
PROGRAM
KEY
PROGRAM KEY
Program Key Operation
Various operating parameters are programmable by the
user. These are modified by pressing the PROGRAM
key and then the
(ENTER) key to enter Program
Mode. A listing of the limits of the programmable val-
ues is found below. Note that the Imperial units are ex-
act values, while Metric units are only approximate.
The ▲ and ▼ (
ARROW) keys are used to scroll
through the user programmable values. A value may be
changed by keying in the new value and pressing the
(ENTER) key to store the new value in memory. The
cursor will be displayed on the screen when a number
key is pressed. The first line of each message will indi-
cate the chiller default (DEF) value), lowest acceptable
programmable value (LO), and highest acceptable pro-
grammable value (HI). The user programmable value
is programmed on in the second line of the message.
When the PROGRAM key is first pressed, the follow-
ing display will appear indicating the user is in the pro-
gram mode:
PROGRAM MODE XXXX
PRESS ENTER KEY TO CONTINUE
Pressing the
(ENTER) key again will display the
first programmable selection.
Suction Pressure Cutout
PROGRAM ◄DEF XXXXX LO XXXXX HI XXXXX
SUCTION PRESSURE CUTOUT = XXX.X PSIG
The suction pressure cutout is protects the chiller from
a low refrigerant condition. It also helps protect from
a freeze-up due to low or no chilled liquid flow. How-
ever, it is only a back-up for a flow switch and cannot
protect against an evaporator freeze under many condi-
tions. This cutout is programmable and should gener-
ally be programmed for 24PSIG (1.65 Barg) for chilled
water cooling.
The cutout is programmable between 24.0 and 36.0
PSIG (1.65 and 2.48 Barg) in the Water Cooling mode
and 5.0 and 36.0 (0.34 and 2.28 Barg) in the Glycol
Cooling mode. The default value for both modes will
be 24.0 PSIG (1.65 Barg) PSIG.
Содержание YCIV0157
Страница 18: ...JOHNSON CONTROLS 18 FORM 201 23 NM2 ISSUE DATE 3 9 2015 SAFETY SYMBOLS THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 38: ...JOHNSON CONTROLS 38 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 42: ...JOHNSON CONTROLS 42 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 50: ...JOHNSON CONTROLS 50 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 104: ...JOHNSON CONTROLS 104 FORM 201 23 NM2 ISSUE DATE 3 9 2015 SECTION 6 TECHNICAL DATA Panel Layout 2 Compressor Models ...
Страница 105: ...JOHNSON CONTROLS 105 SECTION 6 TECHNICAL DATA FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 115: ...JOHNSON CONTROLS 115 SECTION 6 TECHNICAL DATA FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 119: ...JOHNSON CONTROLS 119 SECTION 6 TECHNICAL DATA FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 333: ...JOHNSON CONTROLS 333 FORM 201 23 NM2 ISSUE DATE 3 9 2015 NOTES ...