WRZ-7860-0 Receiver for One-to-One Wireless

Room Sensing Systems Installation Guide

Applications

Use the WRZ-7860-0 Receiver for One-to-One Wireless

Room Sensing Systems to receive wireless Radio

Frequency (RF) temperature and humidity data from WRZ

Series Wireless Room Sensors, and to provide single zone

control data to the specified system digital controllers

in building HVAC systems. The WRZ Series Wireless

Room Sensor and WRZ-7860-0 Receiver combination is

a functional equivalent to a network sensor, such as an

NS-BTP7001-0, but eliminates communications wiring

usually placed inside the wall between the room sensor

and receiver.
Like a network sensor, the WRZ-7860-0 Receiver

communicates over a Sensor Actuator (SA) bus interface

through a MS/TP BACnet

®

 protocol with Johnson

Controls

®

 Controllers. The receiver supplies the sensed

zone temperature and humidity, temperature setpoint,

and occupancy override data.
In a normal application, one WRZ Series Wireless Room

Sensor reports to one WRZ-7860-0 Receiver; however, up

to five WRZ Series Wireless Room Sensors can associate

with a single WRZ-7860-0 Receiver. In multi-sensor

applications, the receiver passes all the room sensors

data to the controller. Configure the Controller to either

average the room sensors temperature and humidity

input, or select the highest or lowest sensed temperature

and humidity for control of the target zone.
The WRZ-7860-0 Receiver uses direct-sequence, spread-

spectrum RF technology, and operates on the 2.4 GHz

Industrial, Scientific, and Medical (ISM) band. The receiver

meets the IEEE 802.15.4 standard for low power, low duty

cycle RF transmitting systems. A WRZ-7860-0 Receiver

operates as a transceiver, to create a bidirectional

association with a WRZ Series Wireless Room Sensor.
Refer to the 

WRZ-7860-0 Receiver for One-to-One Wireless

Room Sensing Systems Technical Bulletin (LIT-12011641)

 for

information about how to commission the WRZ-7860-0

Receiver and configure one-to-one wireless room sensing

systems.

Important: 

The WRZ-7860 Receiver is intended

to provide an input to equipment under normal

operating conditions. Where failure or malfunction

of the receiver could lead to personal injury or

property damage to the controlled equipment or

other property, additional precautions must be

designed into the control system. Incorporate and

maintain other devices, such as supervisory or alarm

systems or safety or limit controls, intended to warn

of or protect against failure or malfunction of the

WRZ-7860 Receiver.

Important: 

Le WRZ-7860 Receiver est destiné à

transmettre des données entrantes à un équipement

dans des conditions normales de fonctionnement.

Lorsqu'une défaillance ou un dysfonctionnement

du receiver risque de provoquer des blessures

ou d'endommager l'équipement contrôlé ou un

autre équipement, la conception du système de

contrôle doit intégrer des dispositifs de protection

supplémentaires. Veiller dans ce cas à intégrer de

façon permanente d'autres dispositifs, tels que

des systèmes de supervision ou d'alarme, ou des

dispositifs de sécurité ou de limitation, ayant une

fonction d'avertissement ou de protection en cas de

défaillance ou de dysfonctionnement du WRZ-7860

Receiver.

North American emissions

compliance

United States

Compliance Statement (Part 15.19)

This device complies with Part 15 of the FCC Rules.

Operation is subject to the following two conditions:

1.  This device may not cause harmful interference, and
2.  This device must accept any interference received,

including interference that may cause undesired

operation.

Warning (Part 15.21)

Changes or modifications not expressly approved by the

party responsible for compliance could void the user’s

authority to operate the equipment.

Canada

Industry Canada Statement(s)

The term 

IC

 before the certification/registration number

only signifies that the Industry Canada technical

specifications were met.
Le terme « IC » précédant le numéro d'accréditation/

inscription signifie simplement que le produit est

conforme aux spécifications techniques d'Industry

Canada.

Installation

To install the WRZ-7860-0 Receiver, follow these guidelines:
• Transport the WRZ-7860-0 Receiver in the original

container to avoid vibration and shock damage to the

receiver.

• Verify that all the parts shipped with the receiver.

• Do not drop the receiver or subject it to physical shock.

*241056347G*

Part No. 24-10563-47 Rev. G

2020-07-09

WRZ-7860-0, WRZ-Mx0100-x, WRZ-RMT10K-2, WRZ-

STR0000-2, WRZ-THx100-0, WRZ-TTx100-0

Содержание WRZ-7860-0

Страница 1: ... malfunction of the receiver could lead to personal injury or property damage to the controlled equipment or other property additional precautions must be designed into the control system Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit controls intended to warn of or protect against failure or malfunction of the WRZ 7860 Receiver Important Le WRZ 7860...

Страница 2: ...s as direct as possible Line of sight is preferred but not required as long as the path is not blocked by large metal objects Mount the receiver so that the antenna symbol on the cover near the LEDs is in a vertical orientation up or down The antenna symbol indicates the approximate location of the receiver s internal onboard antenna Figure 2 Correct mounting orientation If you mount the receiver ...

Страница 3: ...se with screws Wiring The WRZ 7860 0 Receiver has a modular jack on the edge of the enclosure opposite the side with the tamper resistant set screw This modular jack for the SA bus requires a straight through one to one connection cable not a crossover to the SENSOR jack on a Controller Important Configure the field controller as if connected to a wired network sensor Configuring the field control...

Страница 4: ... Troubleshooting Use the status LEDs illustrated in Figure 1 with the information in the following table to troubleshoot the WRZ 7860 0 Receiver Table 2 Status LEDs Name Color Normal Description Flickering SA bus activity SA bus Green Flickering Off steady no SA bus activity Green good room sensor battery 1 blink marginal RF signal strength 2 blinks good RF signal strength 3 blinks excellent RF si...

Страница 5: ...less Room Sensor temperature LCD display F C manual occupancy override button button setpoint adjustment ZFR183x compatible WRZ THB0000 0 Temperature Humidity Sensor with display Warmer Cooler setpoint dial adjustment or scaled setpoint dial adjustment 55 F to 85 F 13 C to 29 C F C button RH button and manual occupancy override button WRZ THN0000 0 Wireless Room Temperature and Humidity Sensor wit...

Страница 6: ...ne RJ 12 Port for SA Communication Bus output sensed zone temperature and humidity temperature setpoint and occupancy override data Temperature sensor accuracy 1 0 F 0 6 C over the range of 55 F to 85 F 13 C to 29 C 1 5 F 0 9 C over the range of 32 F to 55 F 0 C to 13 C and 85 F to 110 F 29 C to 43 C Temperature sensor type Internal 10k ohm Negative Temperature Coefficient NTC thermistor Humidity ...

Страница 7: ...s product constitutes an agreement to such terms Patents Patents https jcipat com Single point of contact APAC Europe NA SA JOHNSON CONTROLS C O CONTROLS PRODUCT MANAGEMENT NO 32 CHANGJIJANG RD NEW DISTRICT WUXI JIANGSU PROVINCE 214028 CHINA JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA Contact information Contact your local branch offi...

Страница 8: ... 2020 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www johnsoncontrols com ...

Отзывы: