Johnson Controls WRZ-7860-0 Скачать руководство пользователя страница 1

WRZ-7860-0 Receiver for One-to-One Wireless Room Sensing Systems 

Installation Instructions

1

 Refer to the 

QuickLIT website

 for the most up-to-date version of this document.

Applications

The WRZ-7860-0 Receiver for One-to-One Wireless Room Sensing Systems is designed to receive wireless Radio 
Frequency (RF) temperature and humidity data from WRZ Series Wireless Room Sensors, and to provide single 
zone control data to specified 

Metasys

® system digital controllers in building HVAC systems. The WRZ Series 

Wireless Room Sensor and WRZ-7860-0 Receiver combination is a functional equivalent to a network sensor, 
such as an NS-BTP7001-0, but eliminates communications wiring (that is usually placed inside the wall) between 
the room sensor and receiver.

Like a network sensor, the WRZ-7860-0 Receiver

 

is designed to communicate over a Sensor Actuator (SA) Bus 

interface via Master-Slave/Token-Passing (MS/TP) BACnet® protocol with Johnson Controls® Variable Air Volume 
(VAV) Modular Assembly (VMA) 16 Series Controllers and Field Equipment Controllers (FECs). The receiver 
supplies the sensed zone temperature and humidity, temperature setpoint, and occupancy override data.

In a typical application, one WRZ Series Wireless Room Sensor reports to one WRZ-7860-0 Receiver; however, up 
to five WRZ Series Wireless Room Sensors can be associated with a single WRZ-7860-0 Receiver. In multi-sensor 
applications, the receiver passes all the room sensors’ data to the controller. The VMA16 Series Controller or FEC 
can be configured to either average the room sensors’ temperature and humidity input, or select the highest or 
lowest sensed temperature and humidity for control of the target zone.

The WRZ-7860-0 Receiver uses direct-sequence, spread-spectrum RF technology, and operates on the 2.4 GHz 
Industrial, Scientific, and Medical (ISM) band. The receiver meets the IEEE 802.15.4 standard for low power, low 
duty cycle RF transmitting systems. A WRZ-7860-0 Receiver operates as a transceiver, to create a bidirectional 
association with a WRZ Series Wireless Room Sensor.

Refer to the 

WRZ-7860-0 Receiver for One-to-One Wireless Room Sensing Systems Technical Bulletin 

(LIT-12011641)

 for information on commissioning the WRZ-7860-0 Receiver and configuring One-to-One wireless 

room sensing systems.

 

  

IMPORTANT:

The WRZ-7860 Receiver is intended to provide an input to equipment under normal operating 

conditions. Where failure or malfunction of the receiver could lead to personal injury or property damage to the 
controlled equipment or other property, additional precautions must be designed into the control system. 
Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, 
intended to warn of or protect against failure or malfunction of the WRZ-7860 Receiver.

IMPORTANT :

Le WRZ-7860 Receiver est destiné à transmettre des données entrantes à un équipement dans 

des conditions normales de fonctionnement. Lorsqu'une défaillance ou un dysfonctionnement du receiver risque 
de provoquer des blessures ou d'endommager l'équipement contrôlé ou un autre équipement, la conception du 
système de contrôle doit intégrer des dispositifs de protection supplémentaires. Veiller dans ce cas à intégrer de 
façon permanente d'autres dispositifs, tels que des systèmes de supervision ou d'alarme, ou des dispositifs de 
sécurité ou de limitation, ayant une fonction d'avertissement ou de protection en cas de défaillance ou de 
dysfonctionnement du WRZ-7860 Receiver.

WRZ-7860-0 Receiver for One-to-One Wireless Room 
Sensing Systems

Installation Instructions

WRZ-7860

-

0

Part No. 24-10563-47, Rev. E

Issued January 2017

24- 10563- 47,  Rev .  E

Содержание WRZ-7860-0

Страница 1: ...pread spectrum RF technology and operates on the 2 4 GHz Industrial Scientific and Medical ISM band The receiver meets the IEEE 802 15 4 standard for low power low duty cycle RF transmitting systems A WRZ 7860 0 Receiver operates as a transceiver to create a bidirectional association with a WRZ Series Wireless Room Sensor Refer to the WRZ 7860 0 Receiver for One to One Wireless Room Sensing System...

Страница 2: ... mounting base Note To avoid damaging the unit do not overtighten the set screw 5 Connect the SA Bus cable from the controller to the WRZ 7860 0 Receiver See Wiring Parts Included The following parts are included one WRZ 7860 0 Receiver with double sided adhesive foam tape factory installed on the back of the unit one installation instructions sheet Compliance Statement Part 15 19 This device comp...

Страница 3: ...nsor whenever possible Signal transmission is best if the path between the room sensor and receiver is as direct as possible Line of sight is desirable but not required as long as the path is not blocked by large metal objects Mount the receiver so that the antenna symbol shown on the cover near the LEDs is in a vertical orientation up or down The antenna symbol indicates the approximate location ...

Страница 4: ...or and a WRZ 7860 0 Receiver If the RF signal path provides unsatisfactory results a Johnson Controls ZFR18xx Series Wireless Field Bus Router can be used as a repeater by locating it between the room sensor and the receiver Surface Mounting the Base with Double Sided Adhesive Foam Tape The WRZ 7860 0 Receiver can be surface mounted using the double sided adhesive foam tape factory installed on th...

Страница 5: ...r jack for the SA Bus requires a straight through One to One connection cable not a crossover to the SENSOR jack on a VMA16 Series Controller or FEC Note The SA Bus cable supplies power to the WRZ 7860 0 Receiver when the VMA16 Series Controller or FEC is powered on For more details on wiring the MS TP Communication Bus refer to the MS TP Communications Bus Technical Bulletin LIT 12011034 Setup an...

Страница 6: ... settings the location and or identification of the controller VMA16 Series or FEC to which the WRZ 7860 0 Receiver is connected by the SA Bus cable Use this information when adjusting the DIP switch settings of the WRZ Series Wireless Room Sensor assigned to the WRZ 7860 0 Receiver and to associate the room sensor and receiver with the correct controller Refer to the WRZ 7860 0 Receiver for One t...

Страница 7: ... Manual Occupancy Override Button and No Display WRZ RMT10K 0 Wireless Remote Temperature Transmitter Display F C Button and Manual Occupancy Override Button For Use with TE 6300 Type II Temperature Sensors Not Included WRZ SST 120 Wireless System Survey Tool WRZ STR0000 0 Wireless Refrigerator Freezer Temperature Transmitter with Probe Assembly Non NIST Certified Display F C Button and Manual Occ...

Страница 8: ...ess Field Bus Router WRZ 7860 0 Receiver for One to One Wireless Room Sensing Systems Part 1 of 2 Field Controller Interface Power and SA Bus Interface between WRZ 7860 0 Receiver and VMA16 Series Controller or FEC Supply Voltage Nominal 15 VDC via the SA Bus 6 7 to 16 5 VDC Required Current Consumption 10 mA Maximum Addressing DIP Switches Field Adjustable for up to 4 096 Unique RF Addresses Ambi...

Страница 9: ...th the essential requirements and other relevant provisions of the R TTE Directive Australia and New Zealand Australia NZ Emissions Compliant Regulatory Compliance Mark RCM Shipping Weight 0 2 lb 0 09 kg The performance specifications are nominal and conform to acceptable industry standards For application at conditions beyond these specifications consult the local Johnson Controls office Johnson ...