Johnson Controls VRF Smart Gateway Скачать руководство пользователя страница 8

Status Indication LEDs

The VRF Smart Gateway communicates status using
LEDs to indicate the following functional states:

power

fault

H-Link bus communication

Ethernet communication

Wi-Fi strength

See the following table for a comprehensive list of VRF
Smart Gateway LED functional information.

VRF Smart Gateway LED Designations and
Descriptions

Table 2: LED Designations and Descriptions

Descriptions/Other
Conditions

Normal

Color

LED
Name

Off = No power

On Steady = Power
supplied by primary
voltage

On Steady
(no flashing)

Green

Power

Off = No faults/normal
operation

On Steady = Missing
hardware, missing
software, operating
system has not yet
initialized, or reset is
in progress.

Slow Flicker (1 blink in
a second) = Software
upgrade in progress

Medium Flicker (2
blinks in a second) =
Startup sequence

Fast Flicker (5 blinks
in a second) = Fault

Off

Red

Fault

Off = No data
transmitting

Flicker = Discovering
VRF devices

On Steady =
Discovery complete

Flicker

Green

H-Link Bus

Table 2: LED Designations and Descriptions

Descriptions/Other
Conditions

Normal

Color

LED
Name

Off = Communication
not established

On Steady =
Communication
established

Flicker = Data
transmission

On Steady

Green

Ethernet

Off = No Wi-Fi signal
or no devices currently
connected over Wi-Fi

Wi-Fi strength is
indicated by the
number of LEDs that
are lit, with one lit LED
indicating weak
wireless signal
strength (between 1%
and 49%) and three lit
LEDs indicating
excellent wireless
signal strength (at
least 75%).

On Steady

Yellow

Wi-Fi

LED Test Sequence at Startup

During startup, the VRF Smart Gateway automatically
initiates a self-test to verify proper operation of the unit.
Immediately after connecting supply power, the following
LED lighting sequence occurs:

1. The Power LED turns on, and stays lit.

2. The Fault LED indicator flashes for approximately 40

seconds, then turns off when the VRF Smart Gateway
is fully functional.

3. The Wi-Fi LEDs light up in succession (scanning),

indicating that the VRF Smart Gateway is waiting for
a device to join its Wi-Fi network.

Repair Information

If the VRF Smart Gateway fails to operate within its
specifications, replace it. The VRF Smart Gateway is not
a serviceable product; however, it does support software
updates to enable feature enhancements. For a
replacement unit, software updates, or accessories,
contact the nearest Johnson Controls representative.

Do not open the VRF Smart Gateway housing. The VRF
Smart Gateway has no user-serviceable parts inside.

8

VRF Smart Gateway Installation Instructions

Содержание VRF Smart Gateway

Страница 1: ...to be up to 30 m 100 ft line of sight away Power must be supplied using the provided external power supply North American Emissions Compliance United States This equipment has been tested and found to...

Страница 2: ...unit upside down which puts the labels upside down Location Considerations Observe the following guidelines when mounting a VRF Smart Gateway Mount the VRF Smart Gateway in areas free of corrosive vap...

Страница 3: ...ace to which the unit is mounted The screw holes on the VRF Smart Gateway can accommodate M3 5 and 6 screws For information on location considerations for maximizing signal strength see the Mounting s...

Страница 4: ...h you are connecting Wiring the H Link Network To wire the H Link Network of the VRF Smart Gateway Connect the two H Link cable wires to the left terminals indicated in the following figure If the VRF...

Страница 5: ...ne disconnection or isolation may be required to completely de energize equipment Contact with components carrying hazardous voltage can cause electric shock and may result in severe personal injury o...

Страница 6: ...overed VRF devices A software update may be available for your device Visit VRFPro com or contact your nearest Johnson Controls representative for the latest version Refer to the VRF Smart Gateway Use...

Страница 7: ...Fi and Ethernet Settings 1 Press and hold the reset button for 6 seconds After 2 seconds the Fault LED displays Slow Flicker behavior This changes to Fast Flicker behavior after an additional 4 second...

Страница 8: ...sion On Steady Green Ethernet Off No Wi Fi signal or no devices currently connected over Wi Fi Wi Fi strength is indicated by the number of LEDs that are lit with one lit LED indicating weak wireless...

Страница 9: ...the corrupted key or certificate to be saved The server detects the error and returns the Error Saving SSL Settings message While this correctly prevents the bad key or certificate from being used it...

Страница 10: ...d Access Pre Shared Key mode Temporal Key Integrity Protocol WPA2 EAP PEAP WPA2 EAP TLS Wireless Security One H Link port 4 pin port Network and Serial Interfaces 145 4 x 85 4 x 40 1 mm 5 72 x 3 36 x...

Страница 11: ...1 ETSI EN301 489 3 Class 2 IEC 60730 1 EN 60730 1 1 Last digit x represents non US country requirements The performance specifications are nominal and conform to acceptable industry standard For appli...

Страница 12: ...Fan Dry Cool Status MI Actual System Mode SYSTEM S 25 High Medium Low Status MI Actual Supply Fan Speed SF SPD 26 50 99 C 58 210 F Value AI Zone Temperature ZN T 27 Dirty Clean Status BI Filter Statu...

Страница 13: ...e INV HRS 11 0 655 350 Hours Value AI Compressor 2 Runtime COMP HRS 12 0 255 Hz Value AI Inverter Compressor Frequency INV FREQ 13 0 65 535 Hz Value AI Total Frequency TOTAL FREQ 14 0 100 Value AI Out...

Страница 14: ...s Enum Value Thermo off 1 Pump down 2 SW on start 3 Thermo on start 4 After defrost 5 Start control 1 6 Start control 2 7 Normal 8 Oil return 9 Defrost ready 1 10 Defrost ready 2 11 Differential press...

Страница 15: ...f synchronism 21 Na4 22 Na5 23 Normal acceleration 24 Normal deceleration 25 Constant speed 26 Overload after the acceleration 27 Overload after the deceleration 28 Overload after constant speed 29 Po...

Страница 16: ...NO 22 BLOCK D NEW DISTRICT WUXI JIANGSU PROVINCE 214142 CHINA JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY Building Technologies Solutio...

Отзывы: