Mounting and Wiring VMA1200 Series Controllers Technical Bulletin

4

 

To change the damper polarity, set the Damper Polarity
configuration property to Reverse, using a Palm™ compatible
handheld device (Version 2.0 or higher operating system) with the
VMA1200 Balancing Tool (VBT) software, the Comm Pro
commissioning tool, or a L

ON

W

ORKS

 Network Services (LNS™)

network management tool.

Note:

 

The default setting for damper polarity is set to normal,

which rotates the damper CCW to close. If it closes in a CW direction,
the damper polarity must be changed.

Wiring and Cabling Precautions

!

  WARNING:

Risk of Electrical Shock.

Disconnect each of multiple power supplies before making electrical
connections. More than one disconnect may be required to completely
de-energize equipment. Contact with components carrying hazardous
voltage can cause electrical shock and may result in severe personal injury
or death.

 

IMPORTANT:

Disconnect all power supplies, as shorting of binary outputs

while energized destroys the VMA triac.

Read these precautions before touching the terminals or wiring the
VMA and its accessories:

 

Make all wiring connections in accordance with the National
Electrical Code (NEC) and state and local regulations. For
transformer primaries above 150 VAC, the secondary must be
earth grounded at the transformer to meet NEC. You can use
Terminal 1 as the earth ground.

Notes:

 

24 VAC to 24 VAC isolation transformers are not necessary.

The power supply is internally isolated. See 

VMA Internal Schematic

Diagram 

in this section.

For specific methods for wiring the VMA to meet
Underwriters Laboratories®, Inc. (UL) 864 requirements, refer to the

Metasys® Smoke Control Wiring Technical Bulletin (LIT-636331).

 

Locate equipment and route the wiring so that sensor signal wiring
is separated from power wiring by 

at least

 150 mm (6 in.).

 

Make all wiring connections to the VMA using only copper
conductors. To establish tight, reliable electrical connections, use
the correct wire sizes for the terminals. Avoid very thin wire, such
as 26 AWG (less than 0.6 mm solid), which tends to break.

 

Follow L

ON

W

ORKS

 Network Bus installation rules for either the

Bus topology or Free topology bus types.

Содержание VMA1200 Series

Страница 1: ...Wiring VMA1200 Series Controllers 2 Introduction 2 Key Concepts 3 VMA Position and Orientation 3 Determine and Set Damper Polarity 3 Wiring and Cabling Precautions 4 VMA Internal Schematic Diagram 6...

Страница 2: ...mbly VMA which is a controller actuator pressure sensor mounts on the Variable Air Volume VAV terminal box and fastens to the damper shaft Instructions for wiring the VMA and its accessory devices are...

Страница 3: ...VMA so that it has adequate clearance for future servicing and is protected from moisture and corrosive fumes Determine and Set Damper Polarity Damper polarity is established upon installation Incorr...

Страница 4: ...d destroys the VMA triac Read these precautions before touching the terminals or wiring the VMA and its accessories Make all wiring connections in accordance with the National Electrical Code NEC and...

Страница 5: ...put Output wiring where convenient The following are additional general wiring considerations The VMA includes an isolated LONWORKS Network Bus isolated binary outputs and isolated 24 VAC See VMA Inte...

Страница 6: ...ed Power Supply 2 Earth Ground Connection 3 Airflow and High Temperature Safety Switches 4 Isolated Triacs and Power Wiring for the Airflow and High Temperature Safety Switches 5 Isolated LONWORKS Net...

Страница 7: ...han 150 VAC 1 2 XFR Synchronous Motor Actuator COM Water Valve 1 2 4 3 In LONWORKS Network Bus VMA 15V 5V Triacs COM COM AO 15 23 14 OPTO 24 VAC BCOM CablePRO or CVTPRO Laptop R R Reheat BO 3 Reheat B...

Страница 8: ...own cable refer to Fabricating Your Own Interconnection Cable in Appendix A Reference Information located in the Variable Air Volume Modular Assembly VMA 1200 Series Overview and Engineering Guidelin...

Страница 9: ...VDC 6 Power Common and Zone Bus Common and Manual Override Common and LED Common 7 Zone Bus 8 LED and Manual Override Manual Override for Temporary Occupied Mode is selected using DIP switches for ei...

Страница 10: ...ional Note The VMA requires a damper shaft protrusion of at least 44 mm 1 3 4 in from the VMA mounting surface 3 Ensure the VMA installation site meets the following environmental requirements The VMA...

Страница 11: ...crew provided into the VMA mounting slot using a power screwdriver and socket with 4 in extension Alternate mounting 1 Perform Step 1 as shown previously 2 Use a punch to mark the position of the shou...

Страница 12: ...elease lever down and position the actuator collar against its internal stop corresponding to the fully closed position This provides a hard stop for this position The hard stop for the open position...

Страница 13: ...A coupler by hand to ensure that the damper can rotate from full closed to full open positions without binding 6 Plug or seal the end of a hollow damper shaft to stop cold duct air from affecting the...

Страница 14: ...2 or 3 position screw terminals or phone cable is to be used See the Variable Air Volume Modular Assembly VMA 1200 Series Overview and Engineering Guidelines Technical Bulletin LIT 1162350 for screw...

Страница 15: ...they are internal and no wiring is required Connecting the LONWORKS Network Bus A connection between the VMA and the Network Control Module NCM is required if the VMA is to communicate with the Metas...

Страница 16: ...Shield LON A LON B LON A LON B NCMConnect To Next L W Compatible Device or NCM ON ORKS Figure 9 Connecting the VMA to an NCM 2 Apply power Locate and observe the VMA LEDs See Tables 7 and 8 for detail...

Страница 17: ...ED SHLD Description LED Color Included on VMA1220 Only Safety Isolation Transformer in Europe Earth Ground COM CW End Stop 3 Controller operating properly The network table is not configured Use Comm...

Страница 18: ...en received Table 8 Running LED Color Name State Description Blinking Application is running normally LED blinks at one second interval On Steady Application is not running Try the following 1 Check t...

Отзывы: