VFD67 Size A to D Getting Started Guide
47
Issue Number: 1
www.johnsoncontrols.com
Sa
fe
Rat
in
Me
ch
El
Ke
yp
Pa
ra
Qu
ick S
D
P
Te
UL L
9
Parameter List
Par
Description
Default
Setting 1
Setting 2
Level 1 parameters
01
Minimum set speed (Hz)
0.0
02
Maximum set speed (Hz)
60.0
03
Acceleration rate (s/100Hz)
33
04
Deceleration rate (s/100Hz)
33
05
Drive configuration
PAd
06
Motor rated current (A)
Drive rating
07
Motor rated speed (rpm)
1800
08
Motor rated voltage (V)
230 / 460
09
Motor power factor (cos
ϕ
)
0.85
10
Parameter access
L1
Level 2 parameters
11
Start/Stop logic select
4
12
Brake controller enable
diS
13
Not used
14
15
Jog reference (Hz)
1.5
16
Analog input 1 mode (mA)
4-.20
17
Enable negative preset speeds
OFF
18
Preset speed 1 (Hz)
0.0
19
Preset speed 2 (Hz)
0.0
20
Preset speed 3 (Hz)
0.0
21
Preset speed 4 (Hz)
0.0
22
Load display units
Ld
23
Speed display units
Fr
24
Customer defined scaling
1.000
25
User security code
0
26
Not used
27
Power up keypad reference
0
28
Parameter copying
no
29
Load defaults
no
30
Ramp mode select
1
31
Stop mode select
1
32
Dynamic V to f select
OFF
33
Catch a spinning motor select
0
34
Terminal B7 mode select
dig
35
Digital output control (terminal B3)
n=0
36
Analog output control (terminal B1)
Fr
37
Maximum switching frequency (kHz)
3
38
Autotune
0
39
Motor rated frequency (Hz)
60.0
40
Number of motor poles
Auto
41
Voltage mode select
Fd
42
Low frequency voltage boost (%)
1.0
43
Serial communications baud rate
19.2
44
Serial comms address
1
45
Software version
46
Brake release current threshold (%)
50
47
Brake apply current threshold (%)
10
48
Brake release frequency (Hz)
1.0
Содержание VFD67 Series