VFD67 Size A to D Getting Started Guide
39
Issue Number: 1
www.johnsoncontrols.com
Sa
fe
Rat
in
Me
ch
El
Ke
yp
P
Qu
ick S
D
P
Te
UL L
6.4
Diagnostic parameters
The following read only (RO) parameters can be used as an aid to fault diagnosis on the
drive. See Figure 8-1
No
Function
Range
Type
81
Frequency reference selected
±Pr
02
Hz
RO
82
Pre-ramp reference
±Pr
02
Hz
RO
83
Post-ramp reference
±Pr
02
Hz
RO
84
DC bus voltage
0 to Drive maximum Vdc
RO
85
Motor frequency
±Pr
02
Hz
RO
86
Motor voltage
0 to Drive rating V
RO
87
Motor speed
±9999 rpm
RO
88
Motor current
+Drive maximum A
RO
89
Motor active current
±Drive maximum A
RO
90
Digital I/O read word
0 to 95
RO
91
Reference enabled indicator
OFF or On
RO
92
Reverse selected indicator
OFF or On
RO
93
Jog selected indicator
OFF or On
RO
94
Analog input 1 level
0 to 100 %
RO
95
Analog input 2 level
0 to 100 %
RO