26
VFD67 Size A to D Getting Started Guide
www.johnsoncontrols.com
Issue Number: 1
Figure 6-4 Pr 05 = Pr (4 presets)
Figure 6-5 Pr 05 = PAd (keypad control)
Setting-up a Forward/Reverse terminal in Keypad mode
From the drive’s display:
•
Set Pr
71
to 8.23
•
Set Pr
61
to 6.33
•
Press the Stop/Reset key
Terminal B5 will now be set-up as a Forward/Reverse terminal
T4
B7
Reference selected
0
0
Preset 1
0
1
Preset 2
1
0
Preset 3
1
1
Preset 4
0V
+10V reference output
+24V output
/Stop
Run
Jog
V
_
+
Analog output
(motor speed)
Digital output
(zero speed)
Not used
Reference select
Reference select
T1
T2
T3
T4
B1
B2
B3
B4
B5
B6
B7
0V
+10V reference output
+24V output
Drive Enable/Reset
V
_
+
Analog output
(motor speed)
Digital output
(zero speed)
Not used
Not used
Not used
Not used
T1
T2
T3
T4
B1
B2
B3
B4
B5
B6
B7
Forward/Reverse