VA9208-GGx-x Series Proportional Electric Spring Return Valve Actuators Installation Instructions 

13

2.

Rotate the switch adjuster until it points to the 
desired switch point.

3.

Connect Auxiliary Switch No. 2 to a power source 
or an ohmmeter and apply power to the actuator. 
The actuator moves to the fully open position and 
holds while power is applied.

4.

Observe the switch point. If required, repeat Step 1 
through Step 3.

Repair Information

A number of replacement parts are available; see 
Table 3 for more details. If an VA9208 Series Electric 
Spring Return Actuator fails to operate within its 
specifications, replace the unit. For a replacement 
electric actuator, contact the nearest Johnson Controls 
representative.

Figure 25:  Switch Trip Point Settings

F

IG

S

W

_

T

R

P

Содержание VA9208-GG Series

Страница 1: ...Electric Spring Return Actuator only to control equipment under normal operating conditions Where failure or malfunction of the electric actuator could lead to personal injury or property damage to th...

Страница 2: ...fy acceptance of exposed plastic materials in plenum areas with the local building authority Building codes for plenum requirements vary by location Some local building authorities accept compliance t...

Страница 3: ...N32 All 5 5 32 131 1 1 32 26 1 23 32 44 7 1 4 184 3 15 16 100 11 32 9 1 31 32 50 1 1 2 DN40 All 5 5 16 135 1 9 64 29 1 57 64 48 7 7 16 189 4 21 64 110 11 32 9 2 11 64 55 2 DN50 2 Way 5 17 32 140 1 15...

Страница 4: ...s be connected to the coil Figure 3 Figure 3 Spring Return VA9208 Actuated VG1241 VG1245 VG1841 and VG1845 Series Ball Valve with Optional M9000 561 Thermal Barrier Installed Dimensions in mm 3 29 32...

Страница 5: ...ds 212 F 100 C See the Mounting the Thermal Barrier section for more information Note Proceed to Step 7 if the ball valve linkage is on actuator Side B 3 Remove the linkage from Side A Figure 5 4 Inse...

Страница 6: ...tor to Spring Return Port A Coil Closed To mount the actuator to spring return port A coil closed 1 Turn the valve stem to the position outlined in Figure 2 Mount optional M9000 561 Thermal Barrier to...

Страница 7: ...0 to 24 lb in 2 3 to 2 7 N m 6 Insert fixed pointer and M4x0 7x83 mm long screw into the Side B actuator hub Direct the arrow on the pointer to 0 7 Install the actuator on the ball valve Tighten the a...

Страница 8: ...instructions Follow the same steps as mounting directly to the valve when mounting the actuator to the thermal barrier Manual Override Use only the supplied manual override crank to reposition the ac...

Страница 9: ...rdement lectrique Plusieurs isolations et d branchements sont peut tre n cessaires pour couper enti rement l alimentation de l quipement Tout contact avec des composants porteurs de tensions dangereus...

Страница 10: ...de to MIN position AC 24 V DC 0 2 10 V DC 0 2 10 V A A Open MIN Position A Closed Normal Operation 1 2 3 4 Y COM U BLK RED GRY ORN Override to MAX position AC 24 V DC 0 2 10 V DC 0 2 10 V C B Closed M...

Страница 11: ...s the full rotation range of 0 to 100 rotation For example if a DC 0 to 10 V input signal is selected and the rotation range is limited to 75 the rotation range limit will be reached at DC 8 3 V Contr...

Страница 12: ...faults to 0 10 V input signal range DA Auxiliary Switch VA9208 xxC 3 Models The VA9208 xxC 3 models include two integral auxiliary switches with a switch adjuster accessible on either face of the actu...

Страница 13: ...ator moves to the fully open position and holds while power is applied 4 Observe the switch point If required repeat Step 1 through Step 3 Repair Information A number of replacement parts are availabl...

Страница 14: ...beled A is Away from Valve CCW Spring Return Actuator Face Labeled B is Away from Valve CW Spring Return Rated Torque Power On Running 70 lb in 8 N m All Operating Temperatures Power Off Spring Return...

Страница 15: ...UL Listed CCN XAPX File E27734 to UL 60730 1A 2003 08 Ed 3 1 Automatic Electrical Controls for Household and Similar Use and UL 60730 2 14 2002 02 Ed 1 Part 2 Particular Requirements for Electric Actu...

Отзывы: