VA9208-GGx-x Series Proportional Electric Spring Return Valve Actuators Installation

Instructions

1

 Refer to the 

QuickLIT website

 for the most up-to-date version of this document.

Applications

The VA9208-GGx-x Series Proportional Electric Spring 
Return Actuators are direct-mount valve actuators that 
operate on AC/DC 24 V power. These bidirectional 
actuators are used to provide accurate positioning on 
Johnson Controls® VG1000 Series 1-1/4, 1-1/2, and 
2 in. (DN32, DN40, and DN50), ball valves in Heating, 
Ventilating, and Air Conditioning (HVAC) applications. 

Integral line voltage auxiliary switches, available only 
on the VA9208-xxC-3 models, indicate end-stop 
position, or perform switching functions within the 
selected rotation range.

VA9208-GGA-2 actuators include plenum-rated cables 
and are specially configured for installation in spaces 
used for environmental air-handling purposes other 
than ducts and plenums as specified in National Fire 
Protection Association (NFPA) 70: National Electrical 
Code section 300.22(C), Other Space Used for 
Environmental Air. The space over a hung ceiling used 
for environmental air handling purposes is an example 
of the type of space for which these actuators are 
configured.

Installation

Install the ball valve with the actuator at or above the 
center line of the horizontal piping (see Figure 1).      

IMPORTANT:

Use this VA9208-GGx-x Series 

Proportional Electric Spring Return Actuator only to 
control equipment under normal operating 
conditions. Where failure or malfunction of the 
electric actuator could lead to personal injury or 
property damage to the controlled equipment or 
other property, additional precautions must be 
designed into the control system. Incorporate and 
maintain other devices, such as supervisory or 
alarm systems or safety or limit controls, intended to 
warn of or protect against failure or malfunction of 
the electric actuator.

IMPORTANT :

Utiliser ce VA9208-GGx-x Series 

Proportional Electric Spring Return Actuator 
uniquement pour commander des équipements 
dans des conditions normales de fonctionnement. 
Lorsqu'une défaillance ou un dysfonctionnement du 
electric actuator risque de provoquer des blessures 
ou d'endommager l'équipement contrôlé ou un autre 
équipement, la conception du système de contrôle 
doit intégrer des dispositifs de protection 
supplémentaires. Veiller dans ce cas à intégrer de 
façon permanente d'autres dispositifs, tels que des 
systèmes de supervision ou d'alarme, ou des 
dispositifs de sécurité ou de limitation, ayant une 
fonction d'avertissement ou de protection en cas de 
défaillance ou de dysfonctionnement du

 

electric 

actuator.

IMPORTANT:

In steam applications, install the 

valve with the stem horizontal to the piping. Failure 
to follow this precaution may shorten the life of the 
actuator.

VA9208-GGx-x Series Proportional Electric Spring Return 
Valve Actuators

Installation Instructions

VA9208-GGA-3, VA9208-GGC-3
VA9208-GGA-2

Part No. 14-1379-21, Rev. F

Release June 2018

14- 1379- 21,  Rev .  F

Содержание VA9208-GG Series

Страница 1: ...Electric Spring Return Actuator only to control equipment under normal operating conditions Where failure or malfunction of the electric actuator could lead to personal injury or property damage to th...

Страница 2: ...fy acceptance of exposed plastic materials in plenum areas with the local building authority Building codes for plenum requirements vary by location Some local building authorities accept compliance t...

Страница 3: ...N32 All 5 5 32 131 1 1 32 26 1 23 32 44 7 1 4 184 3 15 16 100 11 32 9 1 31 32 50 1 1 2 DN40 All 5 5 16 135 1 9 64 29 1 57 64 48 7 7 16 189 4 21 64 110 11 32 9 2 11 64 55 2 DN50 2 Way 5 17 32 140 1 15...

Страница 4: ...s be connected to the coil Figure 3 Figure 3 Spring Return VA9208 Actuated VG1241 VG1245 VG1841 and VG1845 Series Ball Valve with Optional M9000 561 Thermal Barrier Installed Dimensions in mm 3 29 32...

Страница 5: ...ds 212 F 100 C See the Mounting the Thermal Barrier section for more information Note Proceed to Step 7 if the ball valve linkage is on actuator Side B 3 Remove the linkage from Side A Figure 5 4 Inse...

Страница 6: ...tor to Spring Return Port A Coil Closed To mount the actuator to spring return port A coil closed 1 Turn the valve stem to the position outlined in Figure 2 Mount optional M9000 561 Thermal Barrier to...

Страница 7: ...0 to 24 lb in 2 3 to 2 7 N m 6 Insert fixed pointer and M4x0 7x83 mm long screw into the Side B actuator hub Direct the arrow on the pointer to 0 7 Install the actuator on the ball valve Tighten the a...

Страница 8: ...instructions Follow the same steps as mounting directly to the valve when mounting the actuator to the thermal barrier Manual Override Use only the supplied manual override crank to reposition the ac...

Страница 9: ...rdement lectrique Plusieurs isolations et d branchements sont peut tre n cessaires pour couper enti rement l alimentation de l quipement Tout contact avec des composants porteurs de tensions dangereus...

Страница 10: ...de to MIN position AC 24 V DC 0 2 10 V DC 0 2 10 V A A Open MIN Position A Closed Normal Operation 1 2 3 4 Y COM U BLK RED GRY ORN Override to MAX position AC 24 V DC 0 2 10 V DC 0 2 10 V C B Closed M...

Страница 11: ...s the full rotation range of 0 to 100 rotation For example if a DC 0 to 10 V input signal is selected and the rotation range is limited to 75 the rotation range limit will be reached at DC 8 3 V Contr...

Страница 12: ...faults to 0 10 V input signal range DA Auxiliary Switch VA9208 xxC 3 Models The VA9208 xxC 3 models include two integral auxiliary switches with a switch adjuster accessible on either face of the actu...

Страница 13: ...ator moves to the fully open position and holds while power is applied 4 Observe the switch point If required repeat Step 1 through Step 3 Repair Information A number of replacement parts are availabl...

Страница 14: ...beled A is Away from Valve CCW Spring Return Actuator Face Labeled B is Away from Valve CW Spring Return Rated Torque Power On Running 70 lb in 8 N m All Operating Temperatures Power Off Spring Return...

Страница 15: ...UL Listed CCN XAPX File E27734 to UL 60730 1A 2003 08 Ed 3 1 Automatic Electrical Controls for Household and Similar Use and UL 60730 2 14 2002 02 Ed 1 Part 2 Particular Requirements for Electric Actu...

Отзывы: