Section 1: Introduction
1.3 Specifications
Zone Configuration
l
128 wireless zones
l
19 zone types and 4 programmable zone attributes
l
4 touchscreen keypads supported (not evaluated by UL/ULC)
l
4 wirefree keypads (not evaluated by UL/ULC)
l
16 wireless sirens
l
32 wireless keys supported
l
8 wireless repeaters. Note that more than one wireless repeater shall be installed in a given fire alarm signaling sys-
tem to provide a redundant RF transmission path.
Access Codes
l
100 access codes are available, including 99 for standard users and one for the system master user. One installer
code is also provided for the panel, as well as one duress code per partition.
l
Programmable user access levels and partition assignment for each user code
Warning Device Output
l
Integral sounder capable of 85 dB @ 3m
l
2 remote, wireless indoor/outdoor warning devices supported: models PGx901 (indoor), PGx911 (outdoor)
l
Programmable as steady, pulsed, temporal three (as per ISO8201) or temporal four (CO alarm)
l
Warning device sounds alarms in the following priority: Fire, CO, Burglary
Memory
l
128MB RAM
l
4GB eMMC solid-state drive
l
128MB embedded FLASH memory
Power Supply
Transformer:
Primary: 120VAC, 0.35A, 60Hz Class II
Secondary: 12VDC, 1.16A
Standard Battery
l
Model: DSC model 17000178, 7.4V,1.0Ah lithium-Ion, rechargeable (Note: This battery pack shall not be used with
UL/ULC Household Fire Alarm Signaling system)
l
Backup time: 4 hours
l
Recharging time to 85%: 24 hours (UL)
l
Low battery threshold: 7.3V
l
Low battery restore: 7.4V
l
Battery Critical Shutdown: 6.5V
l
Battery lifespan: 3-5 years
Extended Battery
l
Model: DSC model 17000179, 7.4V, 4.5Ah, lithium-Ion, rechargeable
l
Backup time: 24 hours
l
Recharging time to 85%: 24 hours (UL)
l
Low battery threshold: 7.3V
l
Low battery restore: 7.4V
l
Battery Critical Shutdown: 6.5V
l
Battery lifespan: 3-5 years
Operating Environmental Conditions
l
Temperature range: 0°C to +49°C (32°F-120°F)
l
Relative humidity: <93% non condensing
Alarm Transmitter Equipment (ATE) Specification
l
Communications over cellular or Ethernet
l
Supports SIA and Contact ID
l
Complies with TS203 021-1, -2, -3 Telecom equipment requirements
- 4 -