Section 4: Programming Options
Default:
Enabled
Valid range:
Enabled/Disabled
Reed Switch
This option is used to enable/disable the device’s built-in
reed switch. The reed switch is used in conjunction with the
separately mounted magnet as part of the trigger mech-
anism.
If the reed switch is enabled and a device is hardwired to the
external input terminals, both sensors transmit sim-
ultaniously. However, the iotega treats both devices as the
same zone. Disable the reed switch to have the hardwired
device funciton independantly.
Default:
Disabled
Valid range:
Enabled/Disabled
Zone EOL Configuration
This option is used to configure end of line resistors for the
external input terminals. The alarm panel uses EOL resistors
to monitor for fault or alarm conditions.
Default:
EOL Disable
Valid range:
Single, EOL Disable, Normal Open, Normal Close
Shock Accumulation
Shock accumulation is used to count a series of low level
impacts that fall below the programmed alarm threshold
(see Shock Sensitivity) over a ten-second period.
If the total energy of the low level impacts surpasses the
threshold, an alarm is triggered. If not, the accumulation
level is reset.
Default:
Enabled
Valid range:
Enabled/Disabled
Shock Sensitivity Level
This option is used to adjust the sensitivity of the sensor. The
lower the number, the more sensitive the device. Use the
lowest settings for hard surfaces such as concrete.
Default:
8
Valid range:
1-19
4.6.13 Repeater Configuration Options
The following sections are used to program wireless repeat-
ers.
Device Label
This section is used to program a custom label for the
device.
Default:
Repeater X
Valid range:
32 character ASCII
Device Enable/Disable
This option is used to enable and disable the wireless
device.
Default:
Enabled
Valid range:
Enabled/Disabled
- 37 -