Model TFP PH2 — 5.6 K-factor 

Institutional Pendent Sprinklers 

Standard Response, Standard Coverage

Page 1 of 4 

AUGUST 2018 

TFP650

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.
Always refer to Technical Data 

Sheet TFP700 for the “INSTALLER  

WARNING” that provides cautions 

with respect to handling and instal-

lation of sprinkler systems and com-

ponents. Improper handling and 

installation can permanently damage 

a sprinkler system or its compo-

nents and cause the sprinkler to fail  

to operate in a fire situation or cause  

it to operate prematurely.

Worldwide 

Contacts

www.tyco-fire.com

General  

Description

The TYCO Model TFP PH2, 5.6 K-fac-

tor, Institutional Pendent Sprinklers are 

standard response standard coverage, 

fusible solder type spray sprinklers 

designed for use in areas such as cor-

rectional, detention, and mental health 

care facilities.
The unique features of the Model TFP 

PH2 provide a tamper resistant sprin-

kler design that helps eliminate the 

opportunity for individuals to injure 

themselves or others with the compo-

nents of a fire sprinkler. At the same 

time, the Model TFP PH2 optimizes an 

aesthetically appealing flush design 

that conceals most of the operating 

parts.

NOTICE

The Model TFP PH2 Institutional Pendent 

Sprinklers described herein must be 

installed and maintained in compliance 

with this document, as well as with the 

applicable standards of the NATIONAL 

FIRE PROTECTION ASSOCIATION, in 

addition to the standards of any other 

authorities having jurisdiction. Failure to 

do so may impair the performance of 

these devices.
The owner is responsible for maintaining 

their fire protection system and devices 

in proper operating condition. Contact 

the installing contractor or product 

manufacturer with any questions.

Sprinkler 

Identification 

Number (SIN)

TY3290

Technical 

Data

Approvals

UL and C-UL Listed 

NYC under MEA 351-01-E 

(Refer to the Design Criteria section.)

Maximum Working Pressure

175 psi (12,1 bar)

Inlet Thread Connection

1/2 in. NPT

Discharge Coefficient

K=5.6 GPM/psi

½

 (80,6 LPM/bar

½

)

Temperature Ratings

165°F (74°C) or  

212°F (100°C)

Finishes

Sprinkler: Chrome Plated  

Escutcheon: Chrome Plated

Physical Characteristics

Body  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass

Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Deflector Reinforcement 

Bronze

Deflector Post . . . . . . . . . . . . . . . . . . . . . .Bronze

Deflector Post Pin . . . . . . . . . . . . . . . . . . .Bronze

Deflector Core . . . . . . . . . . . . . . . . . . . . . .Bronze

Compression Screw . . . . . . . . . . . . . . . . .Bronze

Lever . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Release Spring . . . . . . . . . . . . . . . . . . . . .Bronze

Core Sleeve . . . . . . . . . . . . . . . . . . . . . . .  Copper
Sealing Assembly . Beryllium Nickel w/ TEFLON

Dust Cover   . . . . . . . . . . . . .Chrome Plated Steel

Fusible Element  . . . . . . . . . . . . .Solder, Copper,  

Stainless Steel

Operation

In the standby condition, the design 

of the Model TFP PH2 is such that a 

dynamic load of 80 lb (36 kg) or more 

applied to the linkage mechanism will 

release the sprinkler. Also, when prop-

erly installed, the escutcheon is held 

fast to the ceiling to deter its removal. 

The shape of the escutcheon cannot 

be easily grasped, which further deters 

tampering.
A fusible solder operating element 

secures the linkage mechanism of the 

Model TFP PH2. When the rated tem-

perature is reached, the solder melts, 

releasing the linkage mechanism that 

holds the sprinkler closed. This allows 

the deflector to extend downward and 

water to flow.

Design 

Criteria

The TYCO Model TFP PH2, 5.6 K-fac-

tor, Institutional Pendent Sprinklers 

(TY3290) are intended for use with 

fire protection systems designed in 

accordance with the standard instal-

lation rules recognized by the appli-

cable Listing or Approval agency (for 

example, Listing is based on NFPA 13 

requirements).