Section 6: Programming
No communications occur for events from a zone in soak test, with the exception of low battery and low battery restore events and
faults generated by low sensitivity in a smoke detector.
A message indicating that the zone is in soak test is displayed when scrolling left or right in the base disarmed keypad menu.
Note:
Soak test is not applied to temperature detector events if it is enabled.
[982] Battery Settings
[000] – Panel Battery Settings
01 – When disabled, the panel battery is charged at 400 mA. When enabled, the battery is charged at 700 mA.
[010] – High Current Output Battery
Enables and disables the high-current battery charge option for HSM2204 1-4.
[020] – 1 A Power Supply Battery
Enables and disables the high-current battery charge option for HSM2300 1-4.
[030] – Corbus Repeater
Enables and disables the high-current battery charge option for HSM3204CX 1-16.
[040] – 3A Power Supply
Enables and disables the high-current battery charge option for HSM33501-4.
Toggle 1 enables high charge for battery 1.
Toggle 2 enables high charge for battery 2.
Toggle 3 enables or disables battery 2. Default is enabled.
Defaults
[989] Default Master Code
This section is used to default the master code to the factory default. After entering this section, key in the installer code then 989.
[989][installer code][989] or [*].
EN
Note:
Feature is only available for models.
[990] Installer Lockout Enable/Disable
When this option is enabled, an installer can not perform a hardware default; attempts to do so are logged to the event buffer.
An audible indication of installer lockout is provided when powering up the alarm system (the phone line relay clicks rapidly).
Software default changes can still be made while installer lockout is enabled.
[990][installer code][990] or [*].
[991] Default Keypads
This programming option is used to return system keypads to factory default settings.
[901]- [932] – Default keypads 1-32
This resets individual keypads to factory defaults. After entering this section, select the keypad to default, key in the installer code then
991 (or press [*]).
[999] – Default all keypads
This section resets all system keypads to factory defaults. After entering this section, enter the installer code then [*] or 991.
[993] Default Alternate Communicator
To reset the alternate communicator to factory defaults, enter [993][installer code][993 or *].
[996] Default Wireless Receiver
To reset the HSM2HOST wireless receiver to factory defaults, enter [996][installer code][996 or *].
[998] Default Audio Module
To reset the HSM2955 audio module to factory defaults, enter [998][installer code][998 or *].
[999] Default System
To reset the alarm controller to factory defaults, enter [999][installer code][999 or *].