Section 6: Programming
ULC
Note:
Must be ON for ULC commercial fire monitoring listed installations.
[382] Communicator Option 3
1 – Reserved
2 – Walk Test Communications
ON: Zone alarms that occur during Walk Test are communicated if programmed to do so.
OFF: Zone alarms during Walk Test are not communicated. FMP key alarms are still communicated.
4 – Call Waiting Cancel
ON: The call waiting cancel string (
See "[304] Call Waiting Cancel String" on page 123
) is used on the first attempt to dial each phone
number. It is not used on any further dialing attempts.
OFF: The call waiting cancel string is not dialed.
5 – Interactive Communicator Enable/Disable
ON: The system communicates using the Alarm.com communicator. All related programming options, reporting, and supervision are
enabled when programmed via PC-Link2.
OFF: The Alarm.com communicator and all associated programming functionality are disabled.
6 – AC Failure Communication Delay in Hours/Minutes
ON: The AC failure communication delay (section [377]>[002] option 2) is programmed in hours.
OFF: The AC failure communication delay is programmed in minutes.
8 – Tamper Limit
ON: When disarmed, the system only communicates module tampers. Zone tampers are not communicated.
OFF: When disarmed, the system communicates all tampers.
[383] Communicator Option 4
1 – Phone Number Account Code
ON: The account code communicated to the central station follows the phone number the event is programmed to communicate on
(programmed in section
"[310] Account Codes" on page 130
):
l
Receiver 1 all events will follow partition 1 account code
l
Receiver 2 all events will follow partition 2 account code
l
Receiver 3 all events will follow partition 3 account code
l
Receiver 4 all events will follow partition 4 account code
OFF: Events follow the account code assigned to each partition when communicating.
Note:
This feature only works with CID
2 – 4 or 6-Digit System Account Code
ON: The programmable account code in section [310][000] is 6 digits long (used for SIA format).
OFF: The programmable account code in section [310][000] is 4 digits long.
3 – Ethernet Enable
ON: Enables the on-board ethernet.
OFF: Disables the on-board ethernet.
4 – Cellular Enable
ON: Enables the plug-in communicator module.
OFF: Disables the plug-in communicator module.
5 – Communicate FTC Events
ON: The alarm system communicates FTC (failure to communicate) events. The FTC Trouble/Restore reporting code transmission
follows the call direction the events are assigned to.
OFF: FTC events are not communicated. FTC Trouble/Restore reporting codes are communicated to the Maintenance call direction
group after the next successful communication.
[384] Communicator Backup Options
2 – Receiver 2 Backup Option
ON: Receiver 2 backs up Receiver 1. Receiver 2 is only used if an FTC event is detected on Receiver 1.
- 135 -