Callout
Description
4
5600 Ω single end-of-line resistor
5
100 Ω alarm initiating loop
6
RM-1 or RM-2 power loop supervisory relay, 12 VDC, 35 mA.
7
Module zone input
Note:
You can manually configure PGM2 as a 2-wire smoke loop in panel programming. If you
configure any zone input as a fire zone, PGM2 is automatically set as a 4-wire smoke detector,
and acts as a power reset. You cannot combine 2-wire detectors and 4-wire smoke or heat
detectors at the same time on the converter.
Wiring auxiliary power
You can use the auxiliary power terminals to power devices such as motion detectors and glass
break detectors. The AUX1 and AUX2 terminals provide a combined current of 700 mA.
Note:
For UL and ULC combination fire and CO and burglary applications, the fire and CO
initiating devices, such as smoke detectors, heat detectors, and CO detectors, must be
powered from a separate output (AUX2) than the burglary initiating devices (AUX1).
Note:
For UL and ULC installations that require 24-hour backup capacity, the maximum AUX
power load cannot exceed a current of 180 mA when using a 7 Ah battery.
Wiring the bell output
You can use the BELL terminals to power a bell, siren, or other device which requires a steady
output voltage when the system is in alarm. The panel provides a current of up to 700 mA.
Note:
A 1 kΩ resistor is required across the BELL+ and BELL- terminals, or the system detects a
trouble condition.
Installing the battery
To install the 12 VDC/ 7 Ah battery in the enclosure, complete the following steps:
Note:
The battery is sold separately.
1. Place the battery on the two plasic supports on the bottom of the enclosure. For more
2. Clip the battery in place.
3.
Optional:
The battery can also be secured in place using a battery strap. To secure the
battery using the battery strap, complete the following steps:
Note:
The battery strap is sold separately.
a.
Place the battery on the two plasic supports on the bottom of the enclosure.
b.
Insert the battery strap through one of the slots.
c.
Wrap the strap around the front of the battery.
d.
Insert the strap through the second slot.
PG8HRDW8 and PG9HRDW8 IQ Hardwire PowerG Wired to Wireless Converter Installation Manual