Figure 12: Wiring the battery
+
-
-
+
-+
Important:
You must maintain a minimum separation of 6.4 mm (0.25 in.) at all
points between non-power limited battery wiring and all other power limited wiring
connections. Do not route any wiring over circuit boards. You must maintain a minimum
separation of 25.4 mm (1 in.) between all wiring and the PCB.
Wiring a keypad/HSM2108/HSM2300
For v1.20 and higher, you can wire a maximum of four keypads to the PG8WLSHW8 or PG9WLSHW8
and a maximum of four HSM2108 and one HSM2300. These modules should be connected to the
Corbus.
Note:
For UL and ULC compliant installations, make sure that the maximum current draw
for the AUX outputs, CORBUS RED and BLK, and any PGM outputs do not exceed the limits in
Table 2. The keypad is only for supplementary use in addition to the panel's user interface. For
information on how to enroll a keypad, see
Enrolling a keypad/zone expander/power supply
.
For information on how to use the keypad, refer to the keypad user manual.
Note:
For UL residential fire applications, ensure that on each zone expanders AUX output or
power supply AUX output fire and burglary devices are not mixed. Only burglary devices or
only fire devices are allowed to be powered from the same AUX output on these modules.
The PG8WLSHW8 or PG9WLSHW8 support the following keypads and modules:
- HS2ICON
- HS2ICONP
- HS2LCD
- HS2LCDP
- HSM2108, HSM2300
PG8WLSHW8 and PG9WLSHW8 IQ Hardwire PowerG Wired to Wireless Converter Installation Manual