T.REX Exit Detector Installation Sheet

Mounting the T.REX

Select an appropriate mounting position. Do not mount the T.REX where there is the potential

for air drafts or objects to pass through gaps around the door and into the detection area.

The cable entry opening into the T.REX is on the right back side, near the cover retaining screw.

There is a recess in the back of the T.REX to allow you to route wires to the cable entry opening.

To mount the T.REX, complete the following steps:

1.

Remove the cover of the T.REX.

2.

Rotate the detector barrel upwards and remove it from the back casing.

3.

Route the wiring into the back casing.

4.

Mount the back casing to the wall.

5.

Install the detector barrel into the back casing and connect the wiring. Ensure that the barrel

can rotate to permit final adjustment.

6. Optional:

Modify the jumper settings. For more information, see Jumper settings.

7.

To replace the cover, first replace the left end that has two hooks.

Jumper settings

There are seven jumpers on the left side of the circuit board. By default, all jumpers are on.

Time
(second
s)

Jumper

A

B

C D

1/2

1

2

3

4

5

6

8

10

15

20

25

30

40

50

60

Indicates jumper on

LED jumper

When the main relay is activated, the jumper selects the LED color. By default, the LED follows the relay activation.

Latch jumper

This jumper determines the relay operation. In the default Latch mode, the relay activates for the duration of the main
relay timer setting whenever someone is detected. If you remove the jumper, it is in Follow mode, and the relay activates
for the duration of activity in the detection zone, up to a maximum time which is equal to the main relay timer setting.

Fast jumper

Use this jumper to select normal or high sensitivity. In the default high sensitivity mode, the LED is red and turns green
when the main relay is activated. Select this mode for exit detector use.

In normal sensitivity mode, the LED is ordinarily green, and turns red when the main relay is activated. Select normal
sensitivity to use the T.REX in unsteady environments.

Main relay timer jumpers

Use these jumpers to set the durations of the relay in Latch or Follow modes. Select from 16 durations, which range
from 1/2 second to 60 seconds. For more information, see Table 1. The default setting is 2 seconds. In both Latch and
Follow modes, when the main relay turns off again, it stays off for 3/4 second. This ensures that the access control panel
does not miss brief changes of state.

Lock control relay (LT2 and XL2 only)

The lock control relay is a normally closed solid state relay which deactivates (open contact) for 2 seconds, 50 ms after a
detection. You cannot modify this time period.

Power-up test

When the T.REX runs its 40-second, power-up diagnostic sequence, the LED flashes twice every second. After the
sequence, the T.REX is ready to operate. If trouble is detected, the LED flashes four times every second. If there is a
strong power fluctuation, the T.REX performs a 10-second self-test and then resumes operations.

1

Table 1: Main relay timer settings