[804][802] Wireless supervisory time window
Before programming the wireless supervisory time window, note the following UL/ULC specifications:
UL/ULCspecifications
Maximumwirelesssupervision time window
ULResidentialBurglary(UL1023)
24hours
Home HealthCare (UL1637)
24 hours
ULC ResidentialBurglary(ULC/ORD-C1023)
24 hours
ULResidentialFire (UL985) installations
200seconds
ULCommercialBurglary(UL1610/UL365)
4hours
ULC ResidentialFire (ULC-S545)
4hours
Table 2: Status LEDs
To program the wireless supervisory time window, complete the following steps:
1.
Enter Installer Programming section [804][802].
2.
Select one of the following options by scrolling or entering the hot key:
l
00–Disabled
l
01–After 1Hour
l
02–After 2Hours
l
03–After 4Hours
l
04–After 8Hours
l
05–After 12Hours
l
06–After 24Hours
3.
Press [*] to accept the selection.
4.
Press [#] to exit the section.
For EN installations, 1 hour or 2 hours must be selected.
When option 06 is used, which configures the system to generate fault conditions after a device has
been detected as absent for 24 hours, smoke detectors generate a fault condition after a maximum of
18 hours when the 200s supervision toggle option is disabled.
[804][810] Wireless Option 1
To program wireless options, complete the following steps:
1.
Enter Installer Programming section [804][810].
2.
Select one of the following options by scrolling or entering the hotkey:
l
01–RF Delinquency
l
02–WirelessSupervisory/RF Jam Alarm
l
03–WirelessTamper
l
04–Fire Supervision
l
05- SmartTemperature Reporting
3.
Press [*] to accept the selection and [#] to exit.
- 11 -