Model ESFR-34

33.6 K-factor Pendent Sprinklers 

Early Suppression, Fast Response

Page 1 of 4 

DECEMBER 2019 

TFP338

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.
Always refer to Technical Data 

Sheet TFP700 for the “INSTALLER  

WARNING” that provides cautions 

with respect to handling and instal-

lation of sprinkler systems and com-

ponents. Improper handling and 

installation can permanently damage 

a sprinkler system or its compo-

nents and cause the sprinkler to fail  

to operate in a fire situation or cause  

it to operate prematurely.

Worldwide 

Contacts

www.tyco-fire.com

Technical 

Data

Approvals

FM Approved

Finish

Natural Brass

Physical Characteristics

Frame  � � � � � � � � � � � � � � � � � � � � � � � � � � � � �Brass

Deflector � � � � � � � � � � � � � � � � � � � � � � � � � �Bronze

Compression Screw � � � � � � � � � �  Stainless Steel

Hook � � � � � � � � � � � � � � � � � � � � � � � � � � � � MONEL

Strut� � � � � � � � � � � � � � � � � � � � � � � � � � � � � MONEL

Link Assembly � � � � � � � � � � � � � � � � Solder, Nickel

Button  � � � � � � � � � � � � � � � � � � � � � Stainless Steel

Sealing Assembly  � �Beryllium Nickel w/TEFLON

Additional Technical Data

See Table A for additional technical data�

Operation

The fusible link assembly is com-

prised of two link halves that are joined 

together by a thin layer of solder� When 

the rated temperature is reached, the 

solder melts and the two link halves 

separate, activating the sprinkler and 

flowing water�

NOTICE

The Model ESFR-34 Sprinklers 

described herein must be installed 

and maintained in compliance with this 

document, as well as with the applica-

ble standards of FM Global, in addi-

tion to the standards of any authorities 

having jurisdiction. Failure to do so 

may impair the performance of these 

devices.
The owner is responsible for main-

taining their fire protection system 

and devices in proper operating con-

dition. Contact the installing contrac-

tor or product manufacturer with any 

questions.
In all cases, the appropriate  FM instal-

lation standard, or other applicable 

standard, must be referenced to ensure 

applicability and to obtain complete 

installation guidelines. The general 

guidelines in this technical data sheet 

are not intended to provide complete 

installation criteria.

Sprinkler 

Identification 

Number

See Table A for sprinkler identification 

number�

General 

Description

TYCO Model ESFR-34 Pendent Sprin-

klers are Early Suppression, Fast 

Response Sprinklers having a nominal 

K-factor of 33�6 (See Figure 1)� They are 

suppression-mode sprinklers that are 

especially advantageous as a means of 

eliminating the use of in-rack sprinklers 

when protecting high-piled storage�
The Model ESFR-34 Sprinklers are pri-

marily used for ceiling-only sprinkler 

protection of (but not limited to) the 

following storage applications:
•  most encapsulated or non-encap-

sulated common materials including 

cartoned, unexpanded plastics

•  uncartoned (exposed) expanded 

plastics in accordance with FM 

Global standards

•  some storage arrangements of 

rubber tires, roll paper, flammable 

liquids, and aerosols

For more specific criteria, refer to Table 

B as well as the applicable design 

standard�
The Model ESFR-34 can protect a 

storage arrangement of 50 ft (15,2 m) 

with a ceiling height of 55 ft (16,8 m) 

without requiring in-rack sprinklers� 

In addition, it can be installed with a 

maximum centerline of thermal sensing 

element-to-ceiling distance of 17 in� 

(432 mm)�