background image

TFP2229

Page 3 of 4

Step D.

 After the ceiling has been 

installed or the finish coat has been 

applied, slide on the Style 20 Closure 

over the Type ULF AM29 Nozzle and 

push the Closure over the Mounting 

Plate until its flange comes in contact 

with the ceiling�

Note:

 Absence of a Style 20 Recessed 

Escutcheon, which is used to cover a 

clearance hole, can delay the time to 

nozzle operation in a fire situation.

Care and 

Maintenance

TYCO Type ULF AM29 AQUAMIST 

Nozzles must be maintained and ser-

viced in accordance with this section� 
Before closing a fire protection system 

main control valve for maintenance 

work on the fire protection system 

that it controls, obtain permission to 

shut down the affected fire protection 

system from the proper authorities 

and notify all personnel who may be 

affected by this action�
Nozzles that are found to be leaking 

or exhibiting visible signs of corrosion 

must be replaced�
Automatic nozzles must never be 

painted, plated, coated, or other-

wise altered after leaving the factory� 

Modified nozzles must be replaced� 

Nozzles that have been exposed to 

corrosive products of combustion but 

have not operated should be replaced 

if they cannot be completed cleaned 

by wiping the nozzle with a cloth or by 

brushing it with a soft bristle brush�
Care must be exercised to avoid 

damage to the nozzles before, during, 

and after installation� Nozzles damaged 

by dropping, striking, wrench twist/

slippage, or the like, must be replaced� 

Also replace any nozzle that has a 

cracked bulb or that has lost liquid from 

its bulb (Ref� Installation section�)
Frequent visual inspections are rec-

ommended to be initially performed 

for nozzles installed in potentially cor-

rosive atmospheres to verify the integ-

rity of the materials of construction 

and finish as they may be affected by 

the corrosive conditions present for a 

given installation� Thereafter, annual 

inspections per NFPA 25 are required, 

in addition to inspections required by 

the authority having jurisdiction�
The owner is responsible for the 

inspection, testing, and maintenance of 

their fire protection system and devices 

in compliance with this document, as 

well as with the applicable standards 

of the NATIONAL FIRE PROTECTION 

ASSOCIATION - for example, NFPA 20, 

25, and 750 - in addition to the stan-

dards of any other authorities having 

jurisdiction� Contact the installing con-

tractor or product manufacturer with 

any questions�
Water mist systems should be in-

spected, tested, and maintained by a 

qualified Inspection Service in accor-

dance with local requirements and/or 

national codes�

Limited 

Warranty

For warranty terms and conditions, visit 

www�tyco-fire�com�

Ordering 

Procedure

Contact your local distributor for avail-

ability� When placing an order, indicate 

the full product name and P/N�

Type ULF AM29  

AQUAMIST Nozzles

Specify: Type ULF AM29 AQUAMIST 

Nozzle with (specify) finish, (specify) 

temperature rating, P/N (specify)

Natural Brass

57°C (135°F) � � � � � � � � � � � � � � P/N 49-029-1-135 

68°C (155°F) � � � � � � � � � � � � � � P/N 49-029-1-155 

79°C (175°F) � � � � � � � � � � � � � � P/N 49-029-1-175 

93°C (200°F)� � � � � � � � � � � � � � P/N 49-029-1-200 

141

°

C (286

°

F) � � � � � � � � � � � � � P/N 49-029-1-286 

182

°

C (360

°

F)� � � � � � � � � � � � � P/N 49-029-1-360

Pure White (RAL 9010) *

57°C (135°F) � � � � � � � � � � � � � � P/N 49-029-3-135 

68°C (155°F) � � � � � � � � � � � � � � P/N 49-029-3-155 

79°C (175°F) � � � � � � � � � � � � � � P/N 49-029-3-175 

93°C (200°F)� � � � � � � � � � � � � � P/N 49-029-3-200

* Eastern Hemisphere sales only

Signal White (RAL 9003) **

57°C (135°F) � � � � � � � � � � � � � � P/N 49-029-4-135 

68°C (155°F) � � � � � � � � � � � � � � P/N 49-029- 4-155 

79°C (175°F) � � � � � � � � � � � � � � P/N 49-029-4-175 

93°C (200°F)� � � � � � � � � � � � � � P/N 49-029-4-200

** Previously known as Bright White

Chrome Plated

57°C (135°F) � � � � � � � � � � � � � � P/N 49-029-9-135 

68°C (155°F) � � � � � � � � � � � � � � P/N 49-029-9-155 

79°C (175°F) � � � � � � � � � � � � � �P/N 49-029-9- 175 

93°C (200°F)� � � � � � � � � � � � � �P/N 49-029-9-200 

141

°

C (286

°

F) � � � � � � � � � � � � � P/N 49-029-9-286 

182

°

C (360

°

F)� � � � � � � � � � � � � P/N 49-029-9-360

Recessed Escutcheon

Specify: Style 20 Recessed Escutch-

eon with (specify*) finish, P/N (specify*)

* Refer to Technical Data Sheet TFP770

Sprinkler Wrenches

Specify: W-Type 6 Sprinkler Wrench, 

P/N 56-000-6-387
Specify: W-Type 7 Recessed Sprinkler 

Wrench, P/N 56-850-4-001