TEC26x7-2 Series BACnet® MS/TP Networked Thermostats with Two Outputs Installation Instructions
9
Table 2: MS/TP Bus Objects (Part 1 of 4)
Point Name
Thermostat Point
(Type/Address)
Range
Room Temp
1, 2
AV 6
-40.0°F/-40.0°C to
122.0°F/50.0°F
Room Temp Override
3
BV 7
0 = Normal
1 = Override
Outdoor Temperature
3, 4
AV 8
-40.0°F/-40.0°C to
122.0°F/50.0°F
Sequence of Operation
MSV 39
1 = Cooling Only
2 = Heating Only
3 = Cooling and Reheat
4 = Heating and Reheat
5 = Cool/Heat Four-Pipe
6 = Cool/Heat Four-Pipe and Reheat
System Mode
MSV 13
1 = Off
2 = Cool
3 = Heat
4 = Auto
Occupancy
MSV 12
1 = Resume Schedule
2 = Occupied
3 = Unoccupied
4 = Temporary Occupied
PI Heating Demand
5
AV 54
0 to 100%
PI Cooling Demand
AV 55
0 to 100%
Supply Temperature
AI 11
-40.0°F/-40.0°C to
122.0°F/50.0°F
AUX (BO5) Status
BI 65
0 = Off
1 = On
AUX (BO5) Output
BV 47
0 = Off
1 = On
Heating (BO3 and BO4) Valve Status
(TEC2627-2 Model)
MSV 66
For On/Off Control:
1 = Open
2 = Closed
For Floating Control:
1 = Stopped
2 = Opening
3 = Closing
Figure 18: Wiring the TEC2647-2 Thermostat for Proportional Control
Two-Pipe Applications
Four-Pipe Applications