TEC2245-4 L

ON

W

ORKS

® Network Thermostat Controller with Single Proportional Output and One-Speed

Fan Control Installation Instructions

9

 

Table 4:  Installer Configuration Menu  (Part 1 of 5)

Parameter 
Appearing 
on Display

Description and Default

Selection Options

Pswrd

Sets the protective access 
password to prevent unauthorized 
access to the Installer Configuration 
Menu.
Default: 

0

Note:

The default setting does not 

lock out access to the Installer 
Configuration Menu.

Range: 

0

 to 

1,000

BI1

Configuration of Binary Input 1.
Default: 

None

(None):

 No function is associated with an input.

(Rem NSB):

 Remote Night Setback (NSB) via a time clock input, an 

occupancy sensor, or from a voltage-free contact. 
Contact open = Occupied; contact closed = Unoccupied.

(MotionNO*):

 Temporary occupancy request via a motion detector 

input. Contact open = Unoccupied. When the contact closes, the 
thermostat controller goes into the occupied mode for a specified 
TOccTime. Once the TOccTime begins, the thermostat controller 
remains in the occupied mode if the contact is open, until the 
TOccTime expires.

(MotionNC*):

 Temporary occupancy request via a motion detector 

input. Contact closed = Unoccupied. When the contact opens, the 
thermostat controller enters occupied mode for a specified TOccTime. 
Once the TOccTime begins, the thermostat controller remains in the 
occupied mode if the contact is closed, until the TOccTime expires.

(Window**):

 Cancels the thermostat controller heating or cooling 

action when a window is open. A Window alarm is displayed indicating 
that the window needs to be closed to resume heating or cooling.
* These settings disable any local override function.
**When this setting is selected, the heating and/or cooling outputs are 
enabled only when the contact is closed. If the fan is set to Auto, it is 
enabled only when the contact is closed. If the fan is set to On, it is not 
affected by this setting.

BI2

Configuration of Binary Input 2.
Default: 

None

(None):

 No function is associated with an input.

(Door Dry): 

Door contact only has an effect if BI1 is set to MotionNO 

or MotionNC. (See the BI1 parameter listed previously in this table.) 
The occupancy is now dictated via BI1 and BI2. Any motion detected 
sets the zone to Occupied status. The zone remains permanently in 
occupied mode until the door contact switch opens momentarily. The 
thermostat then enters stand-by mode. If more movements are 
detected, the occupied mode resumes. While the door is opened, any 
movements detected by the remote PIR sensor or the PIR accessory 
cover are ignored. Use a Normally Closed contact switching device. 
Contact opened = Door opened, 
Contact closed = Door closed.

(RemOVR):

 Temporary occupancy request via a remote input. This 

override function is controlled by a manual remote occupancy 
override. When enabled, this condition disables the override capability 
of the thermostat controller.

(Filter):

 A Filter alarm is displayed. This alarm can be connected to a 

differential pressure switch that monitors a filter.

(Service):

 A Service alarm is displayed on the thermostat controller 

when the input is energized. This input can be tied into the air 
conditioning unit control card, which provides an alarm should there be 
a malfunction.

Содержание TEC2245-4

Страница 1: ...tion to the TEC2245 4 Thermostat Controller IMPORTANT The TEC2245 4 Thermostat Controller is intended to provide an input to equipment under normal operating conditions Where failure or malfunction of the thermostat controller could lead to personal injury or property damage to the controlled equipment or other property additional precautions must be designed into the control system Incorporate an...

Страница 2: ...e thermostat controller mounting base so that the arrow on the base points upward to indicate the top of the thermostat controller Note If you need to install the thermostat on an electrical junction box use 2 1 2 x 4 in 63 x 101 mm square boxes with mud ring covers and avoid smaller 1 1 2 x 4 in 38 x 101 mm or 3 x 2 in 76 x 51 mm square boxes This procedure ensures that you have enough space for ...

Страница 3: ...e screw terminal blocks onto the PCB 4 Reattach the LONWORKS communication wires to the LON terminal block Note If inserting multiple wires into the terminals be sure to properly twist wires together prior to inserting them in the terminal connectors 5 Reattach the thermostat controller cover to the mounting base top side first 6 Use a Phillips head screwdriver to reinstall the security screw on t...

Страница 4: ...abel Function 1 Not used N A 2 Not used N A 3 Fan Fan 4 24V Hot 24 VAC from Transformer 5 24V Common 24 VAC Common from Transformer 6 BO5 Aux BO5 Auxiliary Output 7 BO5 Aux BO5 Auxiliary Output 8 N A N A 9 Not used N A 10 AO1 Cool 11 Not used N A 12 BI1 Configurable Binary Input 1 13 RS Remote Sensor 14 Scom Sensor Common 15 BI2 Configurable Binary Input 2 16 UI3 COS COC SS Not labeled N A LON Net...

Страница 5: ... Fan BO5 Aux BO5 Aux 24 VAC Thermostat Power Fan 24 V Com 0 to 10 VDC 24 VAC Com Analog Output and Valve 24 V Hot AO1 Fan Power and Fan Aux Load BI2 UI3 BI1 Scom OR Remote Inputs SS Supply Sensor COS Change Over Sensor Voltage Free Contact COC NH Normally Heat Closed Contact Cold Water COC NC Normally Cool Closed Contact Hot Water Voltage Free Contact Door Remote Override Filter Alarm Service Alar...

Страница 6: ...ated at the physical end of a LONWORKS network segment unless a terminator is attached Refer to LONWORKS Network Layout Technical Bulletin LIT 1162150 for end of line solutions Setup and Adjustments Thermostat Controller User Interface Keys The TEC2245 4 Thermostat Controller UI consists of five keys on the front cover Figure 7 The function of each key is as follows MODE key toggles among the syst...

Страница 7: ...controller display indicating that the configured password is required to proceed Use the UP DOWN arrow keys to indicate the configured password then press the MODE key to proceed through the Installer Configuration Menu parameters 2 Once the Installer Configuration Menu begins press and release the OVERRIDE key to scroll through the parameters listed in Table 4 3 When the desired parameter is dis...

Страница 8: ...ose 0 Cooling Only Changeover occurs between Cooling Only and Heating Only Table 3 Selection Options for Sequence of Operation Selection Option Control Curve Terminal Numbers Used See Table 1 and Figure 6 0 Cooling Only See Figure 8 10 Proportional Cooling 1 Heating Only See Figure 9 10 Proportional Heating 2 Cooling and Reheat See Figure 10 6 and 7 Reheat 10 Proportional Cooling 3 Heating and Reh...

Страница 9: ...larm is displayed indicating that the window needs to be closed to resume heating or cooling These settings disable any local override function When this setting is selected the heating and or cooling outputs are enabled only when the contact is closed If the fan is set to Auto it is enabled only when the contact is closed If the fan is set to On it is not affected by this setting BI2 Configuratio...

Страница 10: ...ables the Auto function if Option 2 is chosen in the SeqOpera parameter to be visible within the MODE key menu The MODE key is the key at the far left of the thermostat controller cover Default off on The Auto function is active Off Auto Heat Cool Provides automatic changeover between heating and cooling off The auto function is inactive Off Heat Cool C or F Provides temperature scale options for ...

Страница 11: ... temperature in 5 0F 5 0C increments St By CL1 Sets Stand by cooling setpoint limit value is between occupied and unoccupied cooling setpoints Default 78 0 F 25 6 C Range 54 0 F 12 0 C to 100 0 F 37 5 C Unocc HT Sets the Unoccupied Heating setpoint value Default 62 0 F 16 5 C Range 40 0 F 4 5 C to 90 0 F 32 0 C Unocc CL Sets the Unoccupied Cooling setpoint value Default 80 0 F 26 5 C Range 54 0 F ...

Страница 12: ...other use the MODE key to toggle between the two setpoints TOccTime Sets the duration of the Temporary Occupancy Time when the heating or cooling setpoints in the Occupied mode are established by an Override Function enabled in the Main User Menu when the thermostat controller is in the Unoccupied mode a temporary heating or cooling setpoint Default 2 0 hrs Range 0 0 to 24 0 hrs in 1 hour incremen...

Страница 13: ... Used as a diagnostic service help to troubleshoot and diagnose sensor operation Default 40 F 40 C Not applicable 1 This parameter functions only when the TEC is used in conjunction with an onboard occupancy sensor or a remote occupancy sensor Table 4 Installer Configuration Menu Part 5 of 5 Parameter Appearing on Display Description and Default Selection Options Table 5 Accessories Order Separate...

Страница 14: ...tiple Symptoms section of this table A thermostat controller may be connected to the wrong bus TEC2245 4 LONWORKS Network Thermostat Controller with Single Proportional Output and One Speed Fan Control Part 1 of 2 Power Requirements 19 to 30 VAC 50 60 Hz 2 VA Terminals 4 and 5 at 24 VAC Nominal Class 2 or Safety Extra Low Voltage SELV Analog Output Rating 0 to 10 VDC into 2k ohm Resistance Minimum...

Страница 15: ... Part 15 Subpart B Class A LONMARK Certification 3 4 Canada UL Listed File E27734 CCN XAPX7 Under CAN CSA C22 2 No 24 Temperature Indicating and Regulating Equipment Industry Canada ICES 003 Europe CE Mark EMC Directive 2004 108 EC Australia and New Zealand C Tick Mark Australia NZ Emissions Compliant Shipping Weight 0 75 lb 0 34 kg The performance specifications are nominal and conform to accepta...

Отзывы: