background image

TEC22x2-3 L

ON

W

ORKS

® Networked Heat Pump Thermostat Installation Instructions

4

Connecting the L

ON

W

ORKS

 Network

The wiring rules for the L

ON

W

ORKS

 network differ from 

the wiring rules for the Metasys® N2 Bus and the 
BACnet® MS/TP Bus. For more details on wiring the 
L

ON

W

ORKS

 network, refer to the 

L

ON

W

ORKS

 Network 

Layout Technical Bulletin (LIT-1162150)

.

To connect the thermostat to the L

ON

W

ORKS

 network:

1.

Connect the L

ON

W

ORKS

 network wires to the

L

ON

W

ORKS

 network terminal block on the

thermostat (Figure 5, Figure 6, Figure 7, and
Figure 8).

Note:

There is no polarity when connecting the 

L

ON

W

ORKS

 network wires to the thermostat; however, 

we recommend keeping the polarity consistent 
throughout the network. 

2.

After the L

ON

W

ORKS

 network wires are connected

to the first thermostat, continue in a daisy-chained
fashion to the next device.

Note:

The L

ON

W

ORKS

 network wiring must be twisted-

pair lines.

Do not run the L

ON

W

ORKS

 network wiring in the same 

conduit as line voltage wiring (30 VAC or above) or 
other wiring that switches power to highly inductive 
loads (such as contactors, coils, motors, or 
generators).

The L

ON

W

ORKS

 network requires proper termination 

and biasing at the end of a segment (a segment is a 
physically continuous length of wire). The thermostat is 
not equipped with the ability to provide this termination; 
therefore, it cannot be located at the physical end of a 
L

ON

W

ORKS

 network segment unless a terminator is 

attached. Refer to 

L

ON

W

ORKS

 Network Layout 

Technical Bulletin (LIT-1162150)

 for end-of-line 

solutions.

Figure 7: VDC Switching Application for Heat Pumps

Separate 24 VAC

Transformer

Y2

Y1

G

RC

C

RH

W1

O/B

R4

To Auxiliary

Heat Circuit

Heat Pump Terminal Interface

R4-1

R1-1

R2-1

R3-1

R3

R1

R2

Note: 

Use 24 VAC

interface relays R1-1,
R2-1, R3-1, and R4-1
(provided by the user).

Y2

Y1

G

RC

O/B

F

IG

:h

t_

p

m

p

Figure 8: Thermostat to Network Connection

Supervisory 

Controller

Twist wires together 
before inserting them into 
the terminals.

F

IG

:L

O

N

_

w

ir

L

W

ON

ORKS

 

Network Wires

L

W

ON

ORKS

Network 

Terminal Block

L

W

 

Bus Terminals

ON

ORKS

Содержание TEC22 2-3 LonWorks Series

Страница 1: ...appareil num rique de la Classe A respecte toutes les exigences du R glement sur le mat riel brouilleur du Canada Installation Location Considerations Locate the TEC22x2 3 thermostat on a partitioning...

Страница 2: ...into the locking tabs on the thermostat mounting base 9 Pull the pull tabs on each of the connectors and remove the screw terminal blocks as illustrated in Figure 4 Wiring When an existing thermostat...

Страница 3: ...Table 1 Terminal Identification See Figure 5 Number Label Function 1 Y2 Energizes second stage compressor on a call for heating or cooling 2 Y1 Energizes first stage compressor on a call for heating o...

Страница 4: ...k wiring in the same conduit as line voltage wiring 30 VAC or above or other wiring that switches power to highly inductive loads such as contactors coils motors or generators The LONWORKS network req...

Страница 5: ...el when the thermostat is left unattended for 45 seconds Light Emitting Diodes LEDs Three LEDs are included to indicate the fan status call for heat or call for cooling The FAN LED is on when the fan...

Страница 6: ...the UP DOWN arrow keys simultaneously for 5 seconds to broadcast the thermostat s Neuron Identification on the LONWORKS network If the cover is removed you can see a green LED under the LON board fla...

Страница 7: ...ccess No Access System Mode Setting Access No Access No Access Fan Mode Setting Access No Access No Access Schedules Setting5 Access No Access No Access Clock Setting5 Access Access Access Pwr del2 Se...

Страница 8: ...ycle has ended The fan delay is only active when the fan is in the Auto mode TOccTime Sets the duration of the Temporary Occupancy Time when the thermostat is in the Unoccupied mode when a Schedule Ov...

Страница 9: ...desired occupied temperature either at the start of the occupied schedule or after the occupied schedule begins Note Progressive recovery is disabled if either DI1 or DI2 is configured as remote NSB D...

Страница 10: ...auxiliary heat is energized and the heat pump is shut off This typically applies when the air handler heat pump coil is installed after the auxiliary heat There is a 2 minute delay to restart the heat...

Страница 11: ...at is in the unoccupied override mode To resume the schedule while in the Main User Menu 1 Press the NO key to all prompts until the Cancel ovrd Y N prompt appears If the thermostat is in the unoccupi...

Страница 12: ...ess the UP DOWN arrow keys to locate the desired system mode Press the YES key to select the desired system mode 3 Press the YES key to return to the Status Display Menu or press the NO key to return...

Страница 13: ...e to change the time in 1 minute increments press and hold down the keys to change the time in 30 minute increments Note Programming one of the digital inputs to remote NSB disables the menu Table 4 P...

Страница 14: ...ess the UP DOWN arrow keys to set the first unoccupied start time Press the YES key to enter the time RoomTemp 75 0 F Schedule set Y N Monday set Y N Occupied day Y N Occupied 12 00 AM Unoccup 12 00 A...

Страница 15: ...ess the YES key to store the day 6 Press the YES key to choose the time format or press the NO key to access the Main User Menu exit prompt 7 Press the UP DOWN arrow keys to select the desired time fo...

Страница 16: ...voltage between RC and C to be from 19 30 VAC 2 Check for tripped fuse or circuit breaker Overloaded power transformer Verify that the transformer used is powerful enough enough VAs to supply all con...

Страница 17: ...splay Replace the thermostat Auxiliary heat does not operate Wrong mode selected Select Emergency Heat mode Thermostat in Unoccupied mode Select Override to force the thermostat Occupied heating setpo...

Страница 18: ...essages Display Function Service Indicates that there is a service alarm in accordance with the programmable Digital Inputs DI1 or DI2 Filter Indicates that the filter s is dirty in accordance with th...

Страница 19: ...pliant to CFR 47 Part 15 Subpart B Class A LONMARK Certification 3 4 pending Canada UL Listed File E27734 CCN XAPX7 Under CAN CSA C22 2 No 24 Temperature Indicating and Regulating Equipment Industry C...

Отзывы: