background image

TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with

Dehumidification Capability, Fan Control, and Occupancy Sensing Capability

1

Applications

The TEC Series Wireless Thermostat Controller 
System provides wireless networked control of 
Heating, Ventilating, and Air Conditioning (HVAC) 
equipment on a Building Automation System (BAS) 
that enables remote monitoring and programming. This 
TEC Series System integrates into a supervisory 
controller that uses BACnet® Internet Protocol (IP) or 
BACnet Master-Slave/Token-Passing (MS/TP) 
communications.

TEC20 Coordinators allow the supervisory controller to 
communicate with multiple TEC Wireless Thermostat 
Controllers. TEC20x6(H)-4 and TEC20x6H-4+PIR 
Series Wireless Thermostat Controllers control two- or 
four-pipe fan coils, cabinet unit heaters, or other 
equipment using on/off, floating, or proportional 
0 to 10 VDC control input, three speeds of fan control, 
and dehumidification capability. 

The TEC20x6H-4+PIR Series Thermostat Controllers 
have occupancy sensing capability built into the device. 
These devices maximize up to 30% energy savings in 
high-energy usage light commercial buildings, such as 
schools and hotels, during occupied times by using 
additional standby setpoints. See the 

Occupancy 

Sensor Operation – TEC20x6H-4+PIR Series 
Thermostat Controllers

 section for more information.

The wireless mesh network uses ZigBee™ technology 
to enable remote monitoring and programming and to 
enhance reliability by providing redundant transmission 
paths through other TEC Wireless Thermostat 
Controllers, creating a resilient, self-healing mesh 
network. 

North American Emissions Compliance

United States

IMPORTANT:

The TEC20x6(H)-4 and 

TEC20x6H-4+PIR

 

Series Wireless

 

Thermostat 

Controllers are intended to provide an input to 
equipment under normal operating conditions. 
Where failure or malfunction of the thermostat 
controller

 

could lead to personal injury or property 

damage to the controlled equipment or other 
property, additional precautions must be designed 
into the control system. Incorporate and maintain 
other devices, such as supervisory or alarm systems 
or safety or limit controls, intended to warn of or 
protect against failure or malfunction of the 
thermostat controller. 

This equipment has been tested and found to 
comply with the limits for a Class A digital device 
pursuant to Part 15 of the FCC Rules. These limits 
are designed to provide reasonable protection 
against harmful interference when this equipment is 
operated in a commercial environment. This 
equipment generates, uses, and can radiate radio 
frequency energy and, if not installed and used in 
accordance with the instruction manual, may cause 
harmful interference to radio communications. 
Operation of this equipment in a residential area is 
likely to cause harmful interference, in which case 
the user will be required to correct the interference 
at his/her own expense.

RF Transmitters: Compliance Statement (Part 15.19)

This device complies with Part 15 of the FCC Rules. 
Operation is subject to the following two conditions:

1.

This device may not cause harmful interference, and

2.

This device must accept any interference received, 
including interference that may cause undesired 
operation.

Warning (Part 15.21)

Changes or modifications not expressly approved by 
the party responsible for compliance could void the 
user’s authority to operate the equipment

.

TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat 
Controllers with Dehumidification Capability, Fan Control, and 
Occupancy Sensing Capability

Installation Instructions

Part No. 24-9890-1095, Rev. B

Issued July 13, 2010

Supersedes May 17, 2010

Содержание TEC20x6-4 Series

Страница 1: ...less Thermostat Controllers are intended to provide an input to equipment under normal operating conditions Where failure or malfunction of the thermostat controller could lead to personal injury or p...

Страница 2: ...Metasys System Location Guide LIT 12011294 Installing the Thermostat Controller Follow these steps to install the thermostat controller 1 Use a Phillips head screwdriver to remove the security screw...

Страница 3: ...u have enough space for cabling and end of line devices if needed Note For surface mount applications use durable mounting hardware such as Molly bolt anchors that cannot be easily pulled out of the m...

Страница 4: ...ire back into the wall Note Seal the hole in the wall with fireproof material to prevent drafts from affecting the ambient temperature readings 3 Reinsert the screw terminal blocks onto the PCB Note I...

Страница 5: ...EC20x6H 4 PIR Series Thermostat Controller Terminals Figure 6 TEC20x6 H 4 and TEC20x6H 4 PIR Series Thermostat Controller with Separate Power Source for Auxiliary Contact FIG TEC20x6H4_SEP BI2 UI3 BI1...

Страница 6: ...Aux BO5 Aux BO5 Aux Auxiliary Binary Output 8 BO3 BO3 Blank Open Heat 9 Blank BO4 AO2 Close Heat 10 Blank BO1 AO1 Open Cool 11 BO2 BO2 Blank Close Cool 12 BI1 BI1 BI1 Configurable Binary Input 1 13 R...

Страница 7: ...ting Valve 24 V Hot BO3 N C Cooling Valve FIG TEC2016H4_onoff Figure 9 Wiring TEC2026 H 4 TEC2026H 4 PIR TEC2036 H 4 and TEC2036H 4 PIR Thermostat Controllers for On Off Control Two Pipe Applications...

Страница 8: ...key also allows access to the Installer Configuration Menu See the Configuring the Thermostat Controller section C F key hospitality models changes the temperature scale to either Celsius or Fahrenhe...

Страница 9: ...te For models with dehumidification capability the default setting is no humidity reading on the display RH disp parameter is set to off The RH disp parameter must be set to on to display the current...

Страница 10: ...tic LEDs The diagnostic LEDs inside the PIR lens brighten when movement is detected within the first 30 minutes after powerup The LEDs do not light up or brighten after the initial 30 minute period Se...

Страница 11: ...he UP DOWN arrow keys to choose the desired selection option 4 Press and release the center key to continue scrolling through the parameters St By Heat 69 F Occ Heat 72 F Occ Cool 75 F St By Cool 78 F...

Страница 12: ...ration SeqOpera Choose the appropriate sequence of operation The modes presented are user dependent on the sequence of operation selected For two pipe applications using a changeover sensor choose the...

Страница 13: ...Cooling with Reheat See Figure 18 6 and 7 Reheat 10 N O Cooling 11 N C Cooling 6 and 7 Reheat 10 Open Cooling 11 Closed Cooling 6 and 7 Reheat 10 Proportional Cooling 3 Heating with Reheat See Figure...

Страница 14: ...Temperature Increase Increments of 1F 0 5C Heating Setpoint Device Closed Cooling Setpoint Device Opened FIG clng_wth_rht Deadband Reheat On Off Floating or Proportional Outputs Heating Output Cooling...

Страница 15: ...tting Figure 22 This operation applies to the occupied mode when the fan is set to Auto Temperature Increase Increments of 1F 0 5C Heating Setpoint Device Closed Device Closed Device Opened Cooling Se...

Страница 16: ...e fan to low speed the chilled water valve opens to the specified maximum value set by CoolMax the thermostat controller stages Heating to maintain the room temperature at the Cooling setpoint as sens...

Страница 17: ...ted if the Fan Menu parameter is set to 4 On Auto and Auto is the selected fan mode A window alarm appears indicating that the window needs to be closed to resume heating or cooling These settings dis...

Страница 18: ...mperature is available as a point for integration and UI3 Status is not available as a point for integration MenuScro Gives the option of having the display continuously scroll the parameters Default...

Страница 19: ...Only when using a changeover sensor to allow changeover to occur between Cooling Only and Heating Only Choose the selection option 2 Cooling and Reheat when using a changeover sensor to allow changeo...

Страница 20: ...from drifting from stand by mode to unoccupied mode when occupancy sensor functions are used Range 0 0 to 24 0 hours in 0 5 hour increments St By HT Sets Stand by heating setpoint when used with occu...

Страница 21: ...int Adjustment The displayed setpoint is the setpoint from the last action taken by the thermostat controller or the setpoint currently in use Both the heating and cooling setpoints are changed simult...

Страница 22: ...use this selection option 5 Auxiliary On Off control through the auxiliary network command The output can be commanded through the network for any required auxiliary functions via a separate and dedi...

Страница 23: ...e acting 0 to 100 10 to 0 VDC DA Direct acting 0 to 100 0 to 10 VDC Reheat Sets the duty cycle time for reheat output if Option 2 3 or 5 is chosen in the SeqOpera parameter Default 0 1 10 seconds six...

Страница 24: ...y sensing capability 5 TEC 6H PIR Accessory Cover can be used to replace the existing cover on a non PIR TEC20x6H 4 Series Thermostat Controller to provide occupancy sensing capability TEC20x6 H 4 and...

Страница 25: ...le E27734 CCN XAPX Under UL 873 Temperature Indicating and Regulating Equipment FCC Compliant to Part 15 247 Regulations for Low Power Unlicensed Transmitters Transmitter FCC Identification pending Ca...

Отзывы: