TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and
Three Speeds of Fan Control
9
Table 4: Selection Options for Sequence of Operation in Two-Pipe Applications
Selection
Option
Control
Curve
Terminal Numbers Used (See Table 2 and Figure 5.)
On/Off Control
Floating Control
Proportional
0 to 10 VDC Control
(0): Cooling Only
See Figure 13.
10:
Normally Open
(N.O.) Cooling
11:
Normally Closed
(N.C.) Cooling
10:
Open Cooling
11:
Closed Cooling
10:
Proportional Cooling
(1): Heating Only
See Figure 14.
10:
N.O. Heating
11:
N.C. Heating
10:
Open Heating
11:
Closed Heating
10:
Proportional Heating
(2): Cooling and Reheat
See Figure 15.
6 and 7:
Reheat
10:
N.O. Cooling
11:
N.C. Cooling
6 and 7:
Reheat
10:
Open Cooling
11:
Closed Cooling
6 and 7:
Reheat
10:
Proportional Cooling
(3): Heating and Reheat
See Figure 16.
6 and 7:
Reheat
10:
N.O. Heating
11:
N.C. Heating
6 and 7:
Reheat
10:
Open Heating
11:
Closed Heating
6 and 7:
Reheat
10:
Proportional Heating
Table 5: Selection Options for Sequence of Operation in Four-Pipe Applications
Selection
Option
Control
Curve
Terminal Numbers Used (See Table 2 and Figure 5.)
On/Off Control
Floating Control
Proportional
0 to 10 VDC Control
(0): Cooling Only
See Figure 13.
10:
N.O. Cooling
11:
N.C. Cooling
10:
Open Cooling
11:
Closed Cooling
10:
Proportional Cooling
(1): Heating Only
See Figure 14.
8:
N.O. Heating
9:
N.C. Heating
8:
Open Heating
9:
Closed Heating
9:
Proportional Heating
(2): Cooling and Reheat
See Figure 15.
6 and 7:
Reheat
10:
N.O. Cooling
11:
N.C. Cooling
6 and 7:
Reheat
10:
Open Cooling
11:
Closed Cooling
6 and 7:
Reheat
10:
Proportional Cooling
(3): Heating and Reheat
See Figure 16.
6 and 7:
Reheat
8:
N.O. Heating
9:
N.C. Heating
6 and 7:
Reheat
8:
Open Heating
9:
Closed Heating
6 and 7:
Reheat
9:
Proportional Heating
(4): Cool/Heat Four-Pipe
See Figure 17.
8:
N.O. Heating
9:
N.C. Heating
10:
N.O. Cooling
11:
N.C. Cooling
8:
Open Heating
9:
Closed Heating
10:
Open Cooling
11:
Closed Cooling
9:
Proportional Heating
10:
Proportional Cooling
(5): Cool/Heat Four-Pipe
and Reheat
See Figure 18.
6 and 7:
Reheat
8:
N.O. Heating
9:
N.C. Heating
10:
N.O. Cooling
11:
N.C. Cooling
6 and 7:
Reheat
8:
Open Heating
9:
Closed Heating
10:
Open Cooling
11:
Closed Cooling
6 and 7:
Reheat
9:
Proportional Heating
10:
Proportional Cooling