TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and
Three Speeds of Fan Control
17
Cal RH
Sets the desired humidity sensor
calibration (offset). The offset can
be added to or subtracted from the
actual displayed room humidity
(TEC2036-2, TEC2036H-2,
TEC2056-2, and TEC2056H-2
models). This parameter can be
used only if the dehumidification
sequence is enabled.
Default:
0.0% RH
Range:
-15.0% RH
to
15.0% RH
(adjustable in 1% RH increments)
Aux cont
Determines the auxiliary contact
function and configuration.
Default:
0
(0)
Not used,
or used for
reheat
If the sequence of operation is set to
reheat (2, 3, or 5), ignore this parameter.
(1)
Auxiliary
N.O.
Occupied
= contact
closed
Unoccupied
= contact
open
The output
aligns with
occupancy.
(2)
Auxiliary
N.C.
Occupied
= contact open
Unoccupied
= contact
closed
(3*)
Do not use this selection option.
(4*)
Do not use this selection option.
(5)
Auxiliary On/Off control through the
auxiliary network command. The output
can be commanded through the network
for any required auxiliary functions via a
separate and dedicated network
variable.
The output
aligns with
the
secondary
network
occupancy
command.
* If option
(3)
or
(4)
is used, it functions like option
(1)
or
(2)
,
respectively.
FL time
Sets the maximum actuator stroke
timing (floating
CntrlTyp
TEC2026-2, TEC2026H-2,
TEC2036-2, and TEC2036H-2
models).
Default:
1.5 min
Range:
0.5
to
9.0 min
(adjustable in 0.5 minute increments)
Cph
Sets the maximum number of cycles
per hour (TEC2016-2,
TEC2016H-2, and on/off
CntrlTyp
TEC2026-2, TEC2026H-2,
TEC2036-2, and TEC2036H-2
models).
Default:
4
Range:
3
to
8 cycles per hour
RA/DA
Choice of reverse or direct acting
analog output signal (TEC2046-2,
TEC2046H-2, TEC2056-2, and
TEC2056H-2 models).
Default:
DA
(RA):
Reverse acting, 0 to 100% = 10 to 0 VDC
(DA):
Direct acting, 0 to 100% = 0 to 10 VDC
Table 6: Installer Configuration Menu
(Part 6 of 7)
Parameter
Appearing
on Display
Description and Default
Selection Options