TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and
Three Speeds of Fan Control
13
BI1
Configuration of Binary Input 1.
Default:
None
(None):
No function is associated with an input.
(Rem NSB):
Remote Night Setback (NSB) via a time clock input, an
occupancy sensor, or from a voltage-free contact.
Contact open = Occupied; contact closed = Unoccupied.
(MotionNO*):
Temporary occupancy request via a motion detector
input. Contact open = Unoccupied. When the contact closes, the
thermostat controller goes into the occupied mode for a specified
TOccTime. Once the TOccTime begins, the thermostat controller
remains in the occupied mode if the contact is open, until the
TOccTime expires.
(MotionNC*):
Temporary occupancy request via a motion detector
input. Contact closed = Unoccupied. When the contact opens, the
thermostat controller goes into the occupied mode for a specified
TOccTime. Once the TOccTime begins, the thermostat controller
remains in the occupied mode if the contact is closed, until the
TOccTime expires.
(Window):
Cancels the heating or cooling action when a window is
open. The fan operation is only affected if the Fan Menu parameter
is set to (4): On-Auto and Auto is the selected fan mode. A window
alarm appears, indicating that the window needs to be closed to
resume heating or cooling.
*These settings disable any local override function.
BI2
Configuration of Binary Input 2.
Default:
None
(None):
No function is associated with an input.
(Door Dry):
Door contact only has an effect if BI1 is set to
MotionNO
or
MotionNC.
(See the
BI1
parameter earlier in this
table.) The occupancy is now dictated via BI1 and BI2. Any motion
detected sets the zone to Occupied status. The thermostat controller
remains in the occupied mode until a
DoorOpen
is detected, at
which point the thermostat controller goes to the unoccupied mode.
If the door stays open more than the specified door time, the
thermostat controller remains unoccupied. (See the
Door Time
parameter later in this table.)
(RemOVR):
Temporary occupancy request via a remote input. This
override function is controlled by a manual remote occupancy
override. When enabled, this condition disables the override
capability of the thermostat controller.
(Filter):
A Filter alarm is displayed. This alarm can be connected to
a differential pressure switch that monitors a filter.
(Service):
A Service alarm is displayed on the thermostat controller
when the input is energized. This input can be tied into the air
conditioning unit control card, which provides an alarm should there
be a malfunction.
Table 6: Installer Configuration Menu
(Part 2 of 7)
Parameter
Appearing
on Display
Description and Default
Selection Options