TEC2045-4 Wireless Thermostat Controller with Single Proportional Output and One-Speed Fan Control

Installation Instructions

7

Configuring the Sequence of Operation 
(SeqOpera)

Choose the appropriate sequence of operation. The 
modes presented are user-dependent on the sequence 
of operation selected. For applications using a 
changeover sensor, choose the selection option 

(0): Cooling Only

. Changeover occurs between 

Cooling Only

 and 

Heating Only

. See Figure 9 through 

Figure 12 for sequence of operation example.   

   

  

Table 4:  Selection Options for Sequence of Operation 

Selection Option

Control Curve

Terminal Numbers Used
(See Figure 5.)

0: Cooling Only

See Figure 9.

10: 

Proportional Cooling

1: Heating Only

See Figure 10.

10:

 Proportional Heating

2: Cooling and Reheat

See Figure 11.

6 and 7:

 Reheat

10:

 Proportional Cooling

3: Heating and Reheat

See Figure 12.

6 and 7:

 Reheat

10: 

Proportional Heating

Figure 9: Cooling Only

Temperature Increase 

(Increments of 1F°/0.5C°)

Device Closed

Cooling Setpoint

Device Opened

Proportional 

Output

F

IG

:c

ln

g

_

n

ly

Figure 10: Heating Only

Temperature Increase 

(Increments of 1F°/0.5C°)

Device Closed

Heating Setpoint

Device Opened

Proportional 

Output

F

IG

:h

tn

g

_

n

ly

Figure 11: Cooling with Reheat

Temperature Increase 

(Increments of 1F°/0.5C°)

Heating Setpoint

Device 
Closed

Cooling Setpoint

Device 

Opened

F

IG

:c

ln

g

_

w

th

_

rh

t

Deadband

Reheat

Proportional 

Output

Heating Output

Cooling Output

Off

Off

On

On

Figure 12: Heating with Reheat

Temperature Increase 

(Increments of 1F°/0.5C°)

F

IG

:ht

g_

w

th_r

ht

0%

100%

Reheat

Proportional 

Output

Off

Off

On

On

Содержание TEC2045-4

Страница 1: ...ipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful...

Страница 2: ...n the Johnson Controls Portal intranet site Installing the Thermostat Controller Follow these steps to install the thermostat controller 1 Use a Phillips head screwdriver to remove the security screw...

Страница 3: ...ntroller 1 Strip the ends of each wire 6 mm 1 4 in and connect them to the appropriate screw terminals as indicated in Figure 5 2 Carefully push any excess wire back into the wall Note Seal the hole i...

Страница 4: ...11 Blank Close Cool 12 BI1 Configurable Binary Input 1 14 Scom Sensor Common 15 BI2 Configurable Binary Input 2 16 UI3 Configurable Universal Input 3 Figure 6 TEC2045 4 Thermostat Controller with Sep...

Страница 5: ...o the Installer Configuration Menu See the Configuring the Thermostat Controller section UP DOWN arrow keys change the configuration parameters and activate a setpoint adjustment Figure 7 TEC2045 4 Th...

Страница 6: ...To access the Installer Configuration Menu press and hold the OVERRIDE key for approximately 8 seconds Note If the Password parameter is configured Password 0 appears on the thermostat controller dis...

Страница 7: ...Cooling 1 Heating Only See Figure 10 10 Proportional Heating 2 Cooling and Reheat See Figure 11 6 and 7 Reheat 10 Proportional Cooling 3 Heating and Reheat See Figure 12 6 and 7 Reheat 10 Proportiona...

Страница 8: ...ervisory controller Table 5 Installer Configuration Menu Part 1 of 6 Parameter Appearing on Display Description and Default Selection Options Pswrd Sets the protective access password to prevent unaut...

Страница 9: ...or cooling outputs are enabled only when the contact is closed If the fan is set to Auto it is enabled only when the contact is closed If the fan is set to On it is not affected by this setting BI2 Co...

Страница 10: ...the display continuously scroll the parameters Default on off The scroll is inactive on The scroll is active AutoMode Enables the Auto function if Option 2 is chosen in the SeqOpera parameter to be vi...

Страница 11: ...rature in 5 0F 5 0C increments St By CL Sets Stand by cooling setpoint limit value is between occupied and unoccupied cooling setpoints Default 78 0 F 25 6 C Range 54 0 F 12 0 C to 100 0 F 37 5 C Unoc...

Страница 12: ...s the setpoint from the last action taken by the thermostat controller or the setpoint currently in use The heating and cooling setpoints can be separated individually allowing the minimum configured...

Страница 13: ...fan On contact open Unoccupied and fan On or Off contact closed 5 Auxiliary On Off control through the auxiliary network command The output can be commanded through the network for any required auxil...

Страница 14: ...erature Sensor TE 636S 1 Strap Mount Temperature Sensor TEC 6 PIR3 Commercial Fan Coil Controller Cover for Occupancy Sensor TEC20 A 1 Replacement Antenna for TEC20 Coordinator TEC20 RA 14 Remote Ante...

Страница 15: ...aximum 22 AWG 0 6 mm Diameter Recommended Recommended Transmission Range Through Walls 10 m 30 ft Line of Sight Open Space 30 m 100 ft RF Band Direct Sequence Spread Spectrum Transmission 2 4 GHz unli...

Отзывы: