background image

TEC2045-4 Wireless Thermostat Controller with Single Proportional Output and One-Speed Fan Control

Installation Instructions

5

Setup and Adjustments

Thermostat Controller User Interface Keys

The user interface consists of keys on the front cover 
(Figure 8). The function of each key is as follows:

MODE

 key toggles among the system modes 

available, as defined by selecting the appropriate 
operation sequence in the Installer Configuration 
Menu (Off, Heat, Cool, Auto).

FAN

 key toggles between ON and AUTO for fan 

control. ON energizes the fan all the time and 
AUTO operates the fan only on a call for heating or 
cooling, for both occupied and unoccupied periods.

OVERRIDE

 key overrides the unoccupied mode to 

occupied at the local user interface for the 
specified TOccTime. (TOccTime is defined by 
selecting the appropriate time period in the Installer 
Configuration Menu.) If one of the binary inputs is 
configured to operate as a remote override contact, 
this 

OVERRIDE

function is disabled. The 

OVERRIDE

 key also allows access to the Installer 

Configuration Menu. See the 

Configuring the 

Thermostat Controller

 section.

UP/DOWN

 arrow keys change the configuration 

parameters and activate a setpoint adjustment.

Figure 7: TEC2045-4 Thermostat Controller with Same Power Source for Auxiliary Contact

FI

G

:T

E

C20

45_

sm

e

Same 24 VAC

Power Source for Auxiliary Output

(24 VAC Maximum)

24 VAC

Thermostat Power

Fan

24 V~

Com

0 to 10 VDC
24 VAC
Com

Analog Output

and Valve

24 V~

Hot

AO1

Fan

Power and Fan

BO5
Aux

BO5
Aux

Aux Contact
(Isolated Common)
• Reheat
• Lighting
• On/Off Actuation
• Exhaust Fan

 Aux
Load

BI2

UI3

BI1

Scom

- OR -

Remote Inputs

SS (Supply Sensor)
COS (Change Over Sensor)

Voltage-Free
Contact
• COC/NH

 Normally Heat
 Closed Contact

  = Cold Water
• COC/NC
  Normally Cool

 Closed Contact

  = Hot Water

Voltage-Free
Contact
• Door
• Remote
  Override
• Filter Alarm
• Service Alarm

Voltage-Free
Contact
• Remote NSB
• Motion
• Window

Figure 8: Front Cover of TEC2045-4 Thermostat Controller

70.0ºF

Room Temp

FI

G

:T

E

C204

5_w

rl

ss

_f

rnt

v

w

Status LED beneath cover 

indicates network status.

Five keys on the thermostat controller
make operation easy and intuitive.

Backlit, plain text

Liquid Crystal Display (LCD)

is easy to read in any condition.

Light-Emitting Diodes (LEDs)
indicate system activity.

Содержание TEC2045-4

Страница 1: ...ipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful...

Страница 2: ...n the Johnson Controls Portal intranet site Installing the Thermostat Controller Follow these steps to install the thermostat controller 1 Use a Phillips head screwdriver to remove the security screw...

Страница 3: ...ntroller 1 Strip the ends of each wire 6 mm 1 4 in and connect them to the appropriate screw terminals as indicated in Figure 5 2 Carefully push any excess wire back into the wall Note Seal the hole i...

Страница 4: ...11 Blank Close Cool 12 BI1 Configurable Binary Input 1 14 Scom Sensor Common 15 BI2 Configurable Binary Input 2 16 UI3 Configurable Universal Input 3 Figure 6 TEC2045 4 Thermostat Controller with Sep...

Страница 5: ...o the Installer Configuration Menu See the Configuring the Thermostat Controller section UP DOWN arrow keys change the configuration parameters and activate a setpoint adjustment Figure 7 TEC2045 4 Th...

Страница 6: ...To access the Installer Configuration Menu press and hold the OVERRIDE key for approximately 8 seconds Note If the Password parameter is configured Password 0 appears on the thermostat controller dis...

Страница 7: ...Cooling 1 Heating Only See Figure 10 10 Proportional Heating 2 Cooling and Reheat See Figure 11 6 and 7 Reheat 10 Proportional Cooling 3 Heating and Reheat See Figure 12 6 and 7 Reheat 10 Proportiona...

Страница 8: ...ervisory controller Table 5 Installer Configuration Menu Part 1 of 6 Parameter Appearing on Display Description and Default Selection Options Pswrd Sets the protective access password to prevent unaut...

Страница 9: ...or cooling outputs are enabled only when the contact is closed If the fan is set to Auto it is enabled only when the contact is closed If the fan is set to On it is not affected by this setting BI2 Co...

Страница 10: ...the display continuously scroll the parameters Default on off The scroll is inactive on The scroll is active AutoMode Enables the Auto function if Option 2 is chosen in the SeqOpera parameter to be vi...

Страница 11: ...rature in 5 0F 5 0C increments St By CL Sets Stand by cooling setpoint limit value is between occupied and unoccupied cooling setpoints Default 78 0 F 25 6 C Range 54 0 F 12 0 C to 100 0 F 37 5 C Unoc...

Страница 12: ...s the setpoint from the last action taken by the thermostat controller or the setpoint currently in use The heating and cooling setpoints can be separated individually allowing the minimum configured...

Страница 13: ...fan On contact open Unoccupied and fan On or Off contact closed 5 Auxiliary On Off control through the auxiliary network command The output can be commanded through the network for any required auxil...

Страница 14: ...erature Sensor TE 636S 1 Strap Mount Temperature Sensor TEC 6 PIR3 Commercial Fan Coil Controller Cover for Occupancy Sensor TEC20 A 1 Replacement Antenna for TEC20 Coordinator TEC20 RA 14 Remote Ante...

Страница 15: ...aximum 22 AWG 0 6 mm Diameter Recommended Recommended Transmission Range Through Walls 10 m 30 ft Line of Sight Open Space 30 m 100 ft RF Band Direct Sequence Spread Spectrum Transmission 2 4 GHz unli...

Отзывы: