background image

TEC2045-2 Wireless Thermostat Controller with Single Proportional Output and One-Speed Fan Control 
Installation Instructions

2

Mounting

Location Considerations

Locate a thermostat controller:

on a partitioning wall, approximately 1.5 m (5 ft) 
above the floor in a location of average 
temperature

away from direct sunlight, radiant heat, outside 
walls, behind doors, air discharge grills, stairwells, 
or outside doors

away from steam or water pipes, warm air stacks, 
unconditioned areas (not heated or cooled), or 
sources of electrical interference

Allow for vertical air circulation to the thermostat 
controller.

Wireless Signal Transmission Range

Line-of-sight transmission ranges between a 
TEC20 Coordinator and a TEC Wireless Thermostat 
Controller (or between TEC Wireless Thermostat 
Controllers) can be less than the recommended 
distances shown in Table 1. The effective transmission 
range for indoor applications varies because of Radio 
Frequency (RF) signal absorption and reflection due to 
metal obstructions, walls (or floors), and furniture found 
in typical building interiors.

 

For detailed information on locating devices for 
optimum signal strength, refer to the 

Wireless Metasys 

System Location Guide (LIT-12011294), 

which is 

available on the Johnson Controls® Portal intranet site.

Mounting the Thermostat Controller

Follow these steps to mount the thermostat controller:

1.

Use a Phillips-head screwdriver to loosen the 
security screw (if installed) on the bottom of the 
cover.

2.

Pull the bottom edge of the cover and open the 
thermostat controller as illustrated in Figure 1.   

3.

Carefully pull the locking tabs on the right side of 
the mounting base and unlock the Printed Circuit 
Board (PCB). Open the PCB to the left as 
illustrated in Figure 2.

4.

Pull approximately 152 mm (6 in.) of wire from the 
wall, and insert the wire through the hole in the 
mounting base.

5.

Align the mounting base on the wall, and use the 
base as a template to mark the two mounting hole 
locations.

Note:

Be sure to position the mounting base so that 

the arrow on the base points upward to indicate the top 
of the thermostat controller.

6.

Drill a 5 mm (3/16 in.) hole at each of the two 
marked locations, and tap nylon anchors (included) 
flush to the wall surface.

Note:

Other means of anchoring the device may be 

desired, depending on the wall medium.

Table 1:   Recommended Transmission Ranges

Type

Distance

Through Walls

 10 m (32.8 ft)

Open Space

 30 m (98.4 ft)

Figure 1: Removing the Cover

F

IG

:c

v

r_

rm

v

l

Figure 2: Opening the PCB

F

IG

:p

rn

t_

c

ir

c_

b

rd

PCB
Locking
Tabs

Содержание TEC2045-2

Страница 1: ...s equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against har...

Страница 2: ...he Wireless Metasys System Location Guide LIT 12011294 which is available on the Johnson Controls Portal intranet site Mounting the Thermostat Controller Follow these steps to mount the thermostat con...

Страница 3: ...wall Note Seal the hole in the wall with fireproof material to prevent drafts from affecting the ambient temperature readings 3 Reinsert the screw terminal blocks onto the PCB Note If multiple wires a...

Страница 4: ...se Cool 12 BI1 Configurable Binary Input 1 14 Scom Sensor Common 15 BI2 Configurable Binary Input 2 16 UI3 Configurable Universal Input 3 Figure 6 TEC2045 2 Thermostat Controller with Separate Power S...

Страница 5: ...tion Note If one of the binary inputs is configured to operate as a remote override contact this OVERRIDE key is disabled UP DOWN arrow keys change the configuration parameters and activate a setpoint...

Страница 6: ...n press and release the center key to continue scrolling through the parameters Note Pressing the FAN key during configuration restarts the list of displayed parameters at the first parameter listed i...

Страница 7: ...y Temperature Increase Increments of 1F 0 5C Device Closed Heating Setpoint Device Opened Proportional Output FIG htng_nly Figure 11 Cooling with Reheat Temperature Increase Increments of 1F 0 5C Heat...

Страница 8: ...ommunicate with each other Default 0 Range 0 to 500 Note Setting this parameter to 0 disables the function Channel Sets the mesh network channel the device uses for communication Only devices using th...

Страница 9: ...ngeover The contact closes when cold water is present Valid only for two pipe systems COC NC Changeover Contact Normally Cool A dry contact input is used to signal seasonal hot cold water changeover T...

Страница 10: ...UP DOWN arrow keys to change the temperature in 5 0F 5 0C increments Unocc CL Sets the Unoccupied Cooling setpoint value Default 80 0 F 26 5 C Range 54 0 F 12 0 C to 100 0 F 37 5 C Heat max Sets the O...

Страница 11: ...ed and fan On or Off contact closed 5 Auxiliary On Off control through the auxiliary network command The output can be commanded through the network for any required auxiliary functions via a separate...

Страница 12: ...entative Table 6 Display Messages Display Function Service Indicates that there is a service alarm in accordance with the programmable Binary Input BI2 Filter Indicates that the filter s is dirty in a...

Страница 13: ...pen Space 30 m 100 ft RF Band Direct Sequence Spread Spectrum Transmission 2 4 Ghz unlicensed band Transmission Power 10 mW Maximum Resolution 0 1C 0 2F Temperature Range Backlit Display 40 0 C 40 0 F...

Отзывы: