TEC2045-2 Wireless Thermostat Controller with Single Proportional Output and One-Speed Fan Control 
Installation Instructions 

11

Deadband

Sets the minimum deadband 
between the heating and cooling 
setpoints.
Default: 

2.0F°/1.0C°

Range: 

2.0F°/1.0C° 

to 

5.0F°/2.5C°

 (adjustable in 1.0F°/0.5C° 

increments)

Cal RS

Sets the desired room air sensor 
calibration (offset). The offset can 
be added to or subtracted from the 
actual displayed room temperature.
Default: 

0.0F°/0.0C°

Range: -

5.0F°/-2.5C°

 to 

5.0F°/2.5C°

 (adjustable in 1.0F°/0.5C° 

increments)

Aux cont

Determines the auxiliary contact 
function and configuration.
Default: 

0

(0)

Not used, 
or used for 
reheat

If the 

SeqOpera

 is set to reheat (Option 2 

or 3), ignore this parameter.

(1)

Auxiliary 
N.O.

Occupied

 = contact 

closed

Unoccupied

 = contact 

open

The output 
aligns with 
occupancy.

(2)

Auxiliary 
N.C.

Occupied

 = contact open

Unoccupied 

= contact 

closed

(3)

Auxiliary 
N.O.

Occupied and fan On

 = 

contact closed

Unoccupied and fan On 
or Off

 = contact open

The output 
aligns with 
occupancy 
and the 
fan on 
command.

(4)

Auxiliary 
N.C.

Occupied and fan On 

contact open

Unoccupied and fan On 
or Off

 = contact closed

(5)

Auxiliary On/Off control through the 
auxiliary network command. The output 
can be commanded through the network 
for any required auxiliary functions via a 
separate and dedicated network 
variable.

The output 
aligns with 
the 
secondary 
network 
occupancy 
command.

DA/RA

Choice of direct or reverse acting 
analog output signal.
Default: 

DA

(RA):

 Reverse acting, 0 to 100% = 10 to 0 VDC

(DA):

 Direct acting, 0 to 100% = 0 to 10 VDC

Reheat

Sets the duty cycle time for reheat 
output (if Option 2, 3, or 5 is chosen 
in the 

SeqOpera

 parameter).

Default: 

0

(1): 

10 seconds (six cycles per minute), for various equipment with 

solid-state relays that withstand short duty cycles such as electric 
heat.

(0):

 15 minutes (four cycles per hour), for various equipment with 

mechanical relays or contactors controlling mechanical reheat 
systems.

UI3 dis

Displays the supply or changeover 
temperature when UI3 is configured 
as an analog input (supply sensor or 
changeover sensor). Used as a 
diagnostic/service help, to 
troubleshoot and diagnose sensor 
operation.
Default: 

-40°F/-40°C

Used as a diagnostic/service help, to troubleshoot and diagnose 
sensor operation.

Table 5:  Installer Configuration Menu  (Part 4 of 4)

Parameter 
Appearing 
on Display

Description and Default

Selection Options

Содержание TEC2045-2

Страница 1: ...s equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against har...

Страница 2: ...he Wireless Metasys System Location Guide LIT 12011294 which is available on the Johnson Controls Portal intranet site Mounting the Thermostat Controller Follow these steps to mount the thermostat con...

Страница 3: ...wall Note Seal the hole in the wall with fireproof material to prevent drafts from affecting the ambient temperature readings 3 Reinsert the screw terminal blocks onto the PCB Note If multiple wires a...

Страница 4: ...se Cool 12 BI1 Configurable Binary Input 1 14 Scom Sensor Common 15 BI2 Configurable Binary Input 2 16 UI3 Configurable Universal Input 3 Figure 6 TEC2045 2 Thermostat Controller with Separate Power S...

Страница 5: ...tion Note If one of the binary inputs is configured to operate as a remote override contact this OVERRIDE key is disabled UP DOWN arrow keys change the configuration parameters and activate a setpoint...

Страница 6: ...n press and release the center key to continue scrolling through the parameters Note Pressing the FAN key during configuration restarts the list of displayed parameters at the first parameter listed i...

Страница 7: ...y Temperature Increase Increments of 1F 0 5C Device Closed Heating Setpoint Device Opened Proportional Output FIG htng_nly Figure 11 Cooling with Reheat Temperature Increase Increments of 1F 0 5C Heat...

Страница 8: ...ommunicate with each other Default 0 Range 0 to 500 Note Setting this parameter to 0 disables the function Channel Sets the mesh network channel the device uses for communication Only devices using th...

Страница 9: ...ngeover The contact closes when cold water is present Valid only for two pipe systems COC NC Changeover Contact Normally Cool A dry contact input is used to signal seasonal hot cold water changeover T...

Страница 10: ...UP DOWN arrow keys to change the temperature in 5 0F 5 0C increments Unocc CL Sets the Unoccupied Cooling setpoint value Default 80 0 F 26 5 C Range 54 0 F 12 0 C to 100 0 F 37 5 C Heat max Sets the O...

Страница 11: ...ed and fan On or Off contact closed 5 Auxiliary On Off control through the auxiliary network command The output can be commanded through the network for any required auxiliary functions via a separate...

Страница 12: ...entative Table 6 Display Messages Display Function Service Indicates that there is a service alarm in accordance with the programmable Binary Input BI2 Filter Indicates that the filter s is dirty in a...

Страница 13: ...pen Space 30 m 100 ft RF Band Direct Sequence Spread Spectrum Transmission 2 4 Ghz unlicensed band Transmission Power 10 mW Maximum Resolution 0 1C 0 2F Temperature Range Backlit Display 40 0 C 40 0 F...

Отзывы: